VENTING
NOTE: THIS STOVE IS A DIRECT VENT HEATER. ALL COMBUSTION AIR MUST COME DIRECTLY FROM THE OUTSIDE OF THE BUILDING. THE VENT PIPE FOR THIS UNIT CONSISTS OF AN INNER AND AN OUTER PIPE. THE INNER PIPE CARRIES THE STOVE EXHAUST OUT OF THE SYSTEM, AND THE OUTER PIPE BRINGS FRESH COMBUSTION AIR INTO THE STOVE.
AClearance to
BClearance above paved sidewalk or a paved driveway located on public property - 84” (2.1m) minimum
DNot to be installed above a meter/regulator assembly within 36” (914mm) horizontally from the centerline of the regulator
EClearance to service regulator vent outlet - 72” (1.8m) minimum
FClearance above grades, veranda, porch, deck or balcony - 12” (305mm) minimum
GClearance to window or door that may be opened - 12” (305mm) minimum on top and sides and 24” below
HClearance to permanently closed window - 12” (305mm) recommended to prevent condensation on window
IClearance under veranda, porch, deck or balcony - 18” (457mm) minimum if fully open on a minimum two sides beneath the floor
JVertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24” (610mm) from the centerline of the terminal - 18” (457mm) minimum
KClearance to unventilated soffit - 12” (305mm) minimum
LClearance to inside corner - 9” (229mm) minimum
MClearance to a mechanical air supply inlet - 72” (1.8m) minimum
NClearance to outside corner - 6” (152mm) minimum
A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwelling and serves both dwellings (not pictured).
A vent shall not terminate within 36" (914mm) of the property line (not pictured).
For USA installations follow current National Fuel Gas Code ANSI Z223.1.