Quadra-Fire DV-40 manual Venting

Models: DV-40

1 51
Download 51 pages 52.92 Kb
Page 17
Image 17
VENTING

VENTING

NOTE: THIS STOVE IS A DIRECT VENT HEATER. ALL COMBUSTION AIR MUST COME DIRECTLY FROM THE OUTSIDE OF THE BUILDING. THE VENT PIPE FOR THIS UNIT CONSISTS OF AN INNER AND AN OUTER PIPE. THE INNER PIPE CARRIES THE STOVE EXHAUST OUT OF THE SYSTEM, AND THE OUTER PIPE BRINGS FRESH COMBUSTION AIR INTO THE STOVE.

AClearance to non-mechanical air supply inlet to building, or the combustion air inlet to any other stove - 12” (305mm) minimum

BClearance above paved sidewalk or a paved driveway located on public property - 84” (2.1m) minimum

DNot to be installed above a meter/regulator assembly within 36” (914mm) horizontally from the centerline of the regulator

EClearance to service regulator vent outlet - 72” (1.8m) minimum

FClearance above grades, veranda, porch, deck or balcony - 12” (305mm) minimum

GClearance to window or door that may be opened - 12” (305mm) minimum on top and sides and 24” below

HClearance to permanently closed window - 12” (305mm) recommended to prevent condensation on window

IClearance under veranda, porch, deck or balcony - 18” (457mm) minimum if fully open on a minimum two sides beneath the floor

JVertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24” (610mm) from the centerline of the terminal - 18” (457mm) minimum

KClearance to unventilated soffit - 12” (305mm) minimum

LClearance to inside corner - 9” (229mm) minimum

MClearance to a mechanical air supply inlet - 72” (1.8m) minimum

NClearance to outside corner - 6” (152mm) minimum

A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwelling and serves both dwellings (not pictured).

A vent shall not terminate within 36" (914mm) of the property line (not pictured).

For USA installations follow current National Fuel Gas Code ANSI Z223.1.