Quadra-Fire DV-40 manual Installation Into An Existing Masonry Chimney, Vertical Terminations Cont

Models: DV-40

1 51
Download 51 pages 52.92 Kb
Page 27
Image 27
INSTALLATION INTO AN EXISTING MASONRY CHIMNEY

VERTICAL TERMINATIONS (CONT.)

INSTALLATION INTO AN EXISTING MASONRY CHIMNEY

Step 1. Before cutting any holes, assemble the desired sections of direct vent pipe to determine the center of the masonry penetration.

Step 2. Once the center point of the penetration has been determined, cut a 6” (152mm) diameter hole in the masonry. If the hole is too large, the retro connector might not mount properly; if the hole is too small, the appliance might starve for intake air. If there is a frame wall in front of the masonry wall, cut and frame a 10” (254mm) square opening in the wall (centered around the 6” [152mm] masonry opening). If there is sheet rock only (no studs) in front of the masonry the 10” (254mm) opening is still needed, but does not need to be framed. This allows the retro connector to mount directly on the masonry and provide the correct clearances to combustibles (see Figure 22).

FIG. 22

Step 3. Secure the flashing (SDV #705C) to the top of the masonry chimney using a bead of non-hardening sealant-adhesive. If the flashing is larger than the top of the chimney, cut and fold flashing as needed to fit chimney (Figure 23).

Step 4. To determine the length of flex needed, measure from 3” (76mm) above the top of the flashing down to the level of the opening. Add the distance from the center of the chimney out through the wall. Cut a piece of 4” (102mm) flex to this length (extended to its nominal length). Be sure to leave 2”- 3” (51mm-76mm) of flex above the existing chimney to allow for connection to the termination kit.

FIG. 23

Page 27

Page 27
Image 27
Quadra-Fire DV-40 manual Installation Into An Existing Masonry Chimney, Vertical Terminations Cont