Quadra-Fire DV-40 manual Vertical Terminations Cont, Using Gs Series Pipe Cont

Models: DV-40

1 51
Download 51 pages 52.92 Kb
Page 23
Image 23
VERTICAL TERMINATIONS (CONT.)

VERTICAL TERMINATIONS (CONT.)

USING GS SERIES PIPE (CONT.)

Step 4. Assemble the desired lengths of GS pipe and elbows necessary to reach from the stove up through the round support box. Insure that all pipe and elbow connections are in their fully twist- locked position. Be sure to seal the outer pipe with appropriate sealant (high temperature silicone).

Step 5. Cut a hole in the roof centered on the small drill hole placed in the roof in step 2. The hole should be of sufficient size to meet the minimum requirements for clearance to combustibles, as specified. Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support box up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well as above the roofline. The galvanized finish is desirable above the roofline, due to its higher corrosion resistance.

NOTE:

(1)If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3’ (914mm) to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose (Figure 12).

(2)Whenever possible, use 45° elbows, instead of 90° elbows. The 45° elbow offers less restriction to the flow of flue gases and intake air.

Step 6. Slip the flashing over the pipe section(s) protruding through the roof. Secure the base of the flashing to the roof with roofing nails. Insure the roofing material overlaps the top edge of the flashing as shown in Figure 14. Verify that you have at least the minimum clearance to combustibles at the roofline. (See page 17.)

FIG. 14

SHINGLES OVERLAP

TOP EDGE OF FLASHING

Page 23

Page 23
Image 23
Quadra-Fire DV-40 manual Vertical Terminations Cont, Using Gs Series Pipe Cont, Shingles Overlap Top Edge Of Flashing