PRESSURE TESTING
This appliance must be disconnected from the gas supply piping system if any testing is done to the system that exceeds the test pressure of 1/2 PSIG. If the test pressure is less than or equal to 1/2 PSIG, then this appliance must be isolated from the piping system by closing its individual shutoff valve. The gas valve is supplied with pressure test ports for checking input and output pressures. These are located just above the on/off knob and can be found at the rear of the appliance. Pressure can be checked by turning the captured screw counterclockwise two or three turns and then placing the manometer tubing over the test port. The inlet pressure should be checked with the burner lit. BE SURE TO CLOSE CAPTURED SCREWS AFTER TESTING BY TURNING THEM CLOCKWISE. DO NOT OVERTIGHTEN SCREWS.
NOTE: to make flame and heat output adjustments, turn the
NOTICE:
Inlet and Manifold Pressures can only be taken with the burner lit.
OUT | IN |
| IN P U T S ID E |
| T E S T VA LV E |
| O U T P U T S ID E |
| T E S T VA LV E |
(Inlet Pressure)
(Manifold Pressure)
Page 40