Installing the Bridge Hardware
2.4Compatible Modbus Devices and Cables
The Bridge connects directly by RJ45 cable to various products shown in Figure 7.
Table 8 below lists other Modbus devices and their cable connections to the Bridge. Connections are RS±232 unless indicated otherwise.
Cable pinout references are to the diagrams in Figure 8 on page 24.
Table 8 Compatible Modbus Devices and Cables
Device | Device | Cable Pinout |
Part Number | Description | (Figure 8) |
MM±PM10±2xx | PanelMate Plus 1000 (RS232) | A |
MM±PM10±2xx | PanelMate Plus 1000 (RS422) | B |
AS±J478±000 | Modbus Modem, Fixed Modem Control | C |
AS±J478±000 | Modbus Modem, Variable Modem Control | D |
AS±J347±001 | 184/384 Controller Modbus Interface | E |
AS±J375±000 | Micro 84 Controller Modbus Interface | E |
AS±P190±xxx | P190 Programming Panel | E |
AS±884A±xxx | 884 Controller | E |
AS±984x±xxx | 984A, B, X Controller | E |
± ± | PC Serial Port, 9±Pin | F |
AS±P892±000 | ASCII/RIO Interface | G |
140 CPU 424 xx | Quantum Controller, 486 | G |
140 CPU 534 xx | Quantum Controller, 586 | G |
PC±0984±xxx | 984 Controller, 38x/48x/68x/78x Slot Mount | G |
PC±A984±xxx | 984 Controller, Compact | G |
PC±E984±24x/25x | 984 Controller, Compact | G |
PC±E984±455 | 984 Controller, 484 Replacement | G |
PC±M984±xxx | Micro±984 Controller | G |
NW±BM85xxxx | BM85 Bridge Multiplexer | G |
± ± | Generic Modbus Serial Device, 9±Pin | G |
110 VPU 192 00 | Programmer, Handheld | H |
AS±A584±xxx | 584A, L, M Controller | See 584 Note |
TSX SCx | TSX Controllers, Modbus Interface | See TSX Note |
584 Note
Use cable AS±W192±XXX with Adapter 110 XCA 204 02, pinouts in Figure 8 cable E.
TSX Note
TSX Controller products offer multiple options for cable connection to the Bridge. Refer to your product guidebook for more information.
23