Configuring the Bridge

3.5Using the Configuration Menu

When the Bridge enters its configuration mode it displays its opening screen:

Schneider Automation, Inc. ± Modbus Bridge (174 CEV 300 10)

Serial Number 101±161 Software Version V01.00 (990402)

Press Enter to go into Setup Mode, wait to close

At this screen, press <Enter> to see the Configuration Menu.

3.5.1Configuration Menu

The Configuration Menu shows the Bridge's current settings. Here is an example:

Modbus Bridge Firmware Setup, Schneider Automation, Inc.

1)

Network/IP Settings:

 

 

IP Address

192.168.1.23

 

Default Gateway

192.168.1.30

 

Netmask

255.255.255.000

2)

Serial & Mode Settings:

 

 

Protocol

Modbus/RTU, Slave(s) attached

 

Serial Interface

19200,8,E,1,RS232

3)

Modem Control Settings:

 

 

RTS Output

Fixed High/Active

4)

Advanced Modbus Protocol Settings:

 

Slave Addr/Unit ID Source ....

Modbus/TCP header

 

Modbus Serial Broadcasts

Disabled

 

Character, Message Timeout ...

00050 ms, 05000 ms

Commands: D)efault settings,

S)ave, Q)uit without save

Select Command or Parameter (1...4) to change: __

3.5.2Modbus Master Device: Additional Menu Items

If the serial port has already been configured for a Modbus Master device, menu item

4 will omit references to a Slave device, showing only the following:

4) Advanced Modbus Protocol Settings:

Character, Message Timeout ... 00100 ms, 05000 ms

Menu item 5 will show current mapping between Modbus addresses and IP addresses.

5) Unit ID ±> IP Address Table: (followed by the current mapping table).