Using Panel Software
4.2Using Other Software
4.2.1Intellution FIX MMI
The Bridge allows Windows workstations with Intellution FIX software to access Modbus devices by TCP/IP over Ethernet.
The current version of this software does not support the Modbus/TCP Unit_ID field. Therefore if you have configured the Bridge for a Slave device at its serial port, you must configure the Bridge's internal Slave Address parameter for that device. This restricts the Bridge to a single Slave device at its port.
Refer to your software product's documentation for further information.
4.2.2WinTech Modscan
WinTech supplies ModScan32 software, which can select and poll coils and registers from various Modbus RTU/ASCII and Modbus TCP devices.
This software supports the Modbus/TCP Unit_ID field, so RS±485 multiple±drop configurations are supported through the Bridge.
Refer to your software product's documentation for further information.
4.2.3Worderware MMI
The Bridge allows Windows workstations with Wonderware software to access Modbus devices by TCP/IP over Ethernet. You will need the Wonderware Modicon Ethernet I/O Server software, at version 7.0.0.15 or higher.
The current version of this software does not support the Modbus/TCP Unit_ID field. Therefore if you have configured the Bridge for a Slave device at its serial port, you must configure the Bridge's internal Slave Address parameter for that device. This restricts the Bridge to a single Slave device at its port.
Refer to your software product's documentation for further information.
47