Raypak 1334001 Outdoor Water Heaters, High Wind Conditions Outdoor Units Only

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 12
Image 12
Outdoor Water Heaters

Outdoor Water Heaters

These heaters are design certified for outdoor installa- tion. Heaters must not be installed under an overhang of less than three (3) feet from the top on the heater. Three (3) sides must be open in the area under the overhang. Roof water drainage must be diverted away from the heaters installed under overhangs with the use of gutters.

The point from where the flue products exit the heater must be a minimum of four (4) feet below, four (4) feet horizontally from or one (1) foot above any door, win- dow or gravity inlet to a building. The top surface of the heater shall be at least three (3) feet above any forced air inlet, or intake ducts located within ten (10) feet hor- izontally.

Fig. 3: Outdoor Clearances from Openings

High Wind Conditions (Outdoor Units Only)

In areas where high winds are frequent, it may be nec- essary to locate the heater a minimum of 3' from high vertical walls, or install a wind break so the heater is not in direct wind current.

Combustion Air (Indoor Units Only) Air for Combustion and Ventilation

The heater must have both combustion and ventilation air. Minimum requirements for net free air supply openings are 12 inches from ceiling for ventilation and 12 inches from the floor for combustion air as outlined in ANSI Z223.1, and any local codes that may have jurisdiction.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater. Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found in refrigerants, aerosol propellants, dry-cleaning fluids, degreasers, and paint removers. Other harmful elements may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive acid compounds when burned in a gas flame. The resulting acidic condensate can damage or substantially reduce the life of the heater. It may become necessary to provide outside air directly to the heater in order to avoid this problem.

a. All Air From Inside The Building:

Each opening shall have a minimum net free square inches as noted:

 

Square

 

Square

 

Model

Inches

Model

Inches

 

0133

136

1223

1223

 

0182/0181

181

1336

1337

 

0260/0261

264

1468

1467

 

0330/0331

334

1631

1630

 

0400/0401

399

1826

1826

 

0514

512

2100

2100

 

0624

627

2500

2499

 

0724

726

3001

3000

 

0824

825

3500

3500

 

0962

962

4001

4000

 

1125

1125

 

 

 

BOLD TYPE indicates Low NOx models.

Table E: All Air From Inside The Building

b. All Air From Outdoors:

When air is supplied directly from outside of building, each opening shall have a minimum net free square inches as noted:

 

Square

 

Square

 

Model

Inches

Model

Inches

 

0133

34

1223

306

 

0182/0181

46

1336

335

 

0260/0261

66

1468

367

 

0330/0331

84

1631

408

 

0400/0401

100

1826

457

 

0514

128

2100

525

 

0624

157

2500

625

 

0724

182

3001

750

 

0824

207

3500

875

 

0962

241

4001

1000

 

1125

282

 

 

 

BOLD TYPE indicates Low NOx models.

Table F: All Air From Outdoors

12

Page 12
Image 12
Raypak 1334001 operating instructions Outdoor Water Heaters, High Wind Conditions Outdoor Units Only