Raypak 1334001 operating instructions Piping-DomesticHot Water Supply Heaters

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 23
Image 23
Piping—Domestic Hot Water Supply Heaters

 

 

 

 

 

 

 

 

WATER HARDNESS

 

 

 

 

 

 

MODELS

 

 

SOFT

 

 

 

 

MEDIUM

 

 

 

 

 

HARD

 

 

 

 

 

0-4 Grains Per Gallon

 

 

5-15 Grains Per Gallon

 

 

16-25 Grains Per Gallon*

 

Indoor

Outdoor

T

GPM

P

MPS

SHL

T

GPM

P

 

MPS

 

SHL

T

GPM

P

MPS

SHL

0133

0133

22

10

3.4

1-1/4

5.1

17

13

5.5

 

1-1/4

 

8.2

10

22

14.7

1-1/4

22.0

0182/0181

0182

15

20

1.8

1-1/2

4.6

12

26

3.1

 

1-1/2

 

7.5

7

45

9.2

1-1/2

20.8

0260/0261

0260

21

20

1.9

1-1/2

4.6

17

26

3.1

 

1-1/2

 

7.6

10

45

9.4

1-1/2

21.0

0330/0331

0330

27

20

1.9

1-1/2

4.7

21

26

3.2

 

1-1/2

 

7.7

12

45

9.6

1-1/2

21.2

0400/0401

0400

30

22

2.3

1-1/2

5.6

25

26

3.3

 

1-1/2

 

7.8

15

45

9.8

1-1/2

21.3

0514

0514

20

42

2.0

2

4.8

16

52

3.0

 

2

 

7.1

9

90

9.0

2

19.1

0624

0624

25

41

2.0

2

4.7

19

54

3.4

 

2

 

7.9

11

90

9.5

2

20.9

0724

0724

29

41

2.1

2

4.9

20

60

4.4

 

2

 

9.8

13

90

10.0

2

21.4

0824

0824

30

45

2.6

2

5.9

20

68

6.0

 

2

 

12.8

15

90

10.5

2

21.9

0962

0926

30

53

3.8

2-1/2

5.3

20

79

8.5

 

2-1/2

 

11.5

18

90

11.0

2-1/2

15.2

1125

1083

30

61

5.5

2-1/2

7.5

20

90

12.0

 

2-1/2

 

16.2

20

90

12.0

2-1/2

16.2

1223

1178

30

67

7.0

2-1/2

9.3

22

90

12.5

 

2-1/2

 

16.7

22

90

12.5

2-1/2

16.7

1336

1287

30

73

8.7

2-1/2

11.5

24

90

13.3

 

2-1/2

 

17.5

24

90

13.3

2-1/2

17.5

1468

1414

30

80

11.0

2-1/2

14.4

27

90

14.0

 

2-1/2

 

18.2

27

90

14.0

2-1/2

18.2

1631

1571

30

90

14.8

2-1/2

19.0

30

90

14.8

 

2-1/2

 

19.0

30

90

14.8

2-1/2

19.0

1826

1758

33

90

15.4

2-1/2

19.6

33

90

15.4

 

2-1/2

 

19.6

33

90

15.4

2-1/2

19.6

2100

N/A

30

115

5.0

3

7.9

20

172

11.0

 

3

 

17.2

17

200

14.8

3

22.9

2500

N/A

30

137

7.5

3

11.4

20

200

15.8

 

3

 

23.9

20

200

15.8

3

23.9

3001

N/A

30

164

11.2

3

17.0

25

200

16.7

 

3

 

24.8

25

200

16.7

3

24.8

3500

N/A

30

191

16.2

3

23.7

29

200

17.5

 

3

 

25.6

29

200

17.5

3

25.6

4001

N/A

33

200

18.7

3

26.8

33

200

18.7

 

3

 

26.8

33

200

18.7

3

26.8

BOLD TYPE indicates Low NOx models.

ΔT = Temperature Rise, Degree F@GPM FLOW GPM = Gallons per Minute Flow

ΔP = Pressure Drop, Foot thru Heat Exchanger MPS = Minimum Pipe Size, NPT

SHL = System Head Loss

*Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.

Table I: General Specifications Uni-Temp 80 Hot Water Supply Systems

Piping—Domestic Hot Water Supply Heaters

Table I above provides data for selecting in-line pumps for use in a Uni-Temp 80 system for a single heater and tank according to the following:

1.Flow rates are based on water hardness as meas- ured in grains per gallon.

Soft: 0-4 grains per gallon.

Medium: 5-15 grains per gallon.

Hard: 16-25 grains per gallon.

2.Maximum Flow Rates:

0133

22 GPM

0181-0401

45 GPM

0514-1826

90 GPM

2100-4001

200 GPM

3.Pressure drop values (ΔP and SHL) and minimum pipe sizes are for two-pass heaters.

4.Sizing based on heater and tank being placed 5 feet apart. The equivalent length of pipe, valves and fittings in the system is as follows:

1-1/2" NPT = 70 Ft (0181-0401)

2" NPT = 75 Ft (0514-0824)

2-1/2" NPT = 80 Ft (0926-1826)

3" NPT = 85 Ft (2100-4001)

Additional pipe fittings will increase the system head loss.

5.Select a pump based on the water hardness, flow, and system head loss.

6.If heater is more than two stories above the tank, consult the factory.

NOTE: GPM flow rates are limited by maximum acceptable velocity through heat exchanger tubes. Heater models 0514 through 1826 may be provided with an integral rear-mounted pump. This must be specified at time of order.

MINIMUM INPUT ADJUSTMENT: Model Types WH have minimum input ratings as specified on their indi- vidual rating plates. Minimum input controllers have been pre-set at the factory. Consult with factory repre- sentatives if a minimum input problem should occur.

23

Page 23
Image 23