Flow Rates

 

 

 

 

 

 

 

 

 

MAXIMUM AND MINIMUM FLOW RATES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-PASS HEAT EXCHANGER

 

 

 

 

 

1-PASS HEAT EXCHANGER

 

 

 

MODEL

 

 

MAX

 

 

 

 

MIN

 

 

 

 

HDR

 

 

 

 

MAX

 

 

 

MIN

 

 

HDR

 

SIZE

 

GPM

T

P FT

 

GPM

T

P FT

 

CONN

 

 

GPM

T

P FT

 

GPM

T

P FT

 

CONN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0133*

 

 

22

10

14.7

 

 

10

22

3.3

 

 

 

1-1/4"

 

 

 

 

 

 

 

 

 

 

 

 

0182/0181

 

45

7

9.2

 

 

20

15

1.8

 

 

 

1-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

0260/0261

 

45

10

9.4

 

 

20

22

1.9

 

 

 

1-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

0330/0331

 

45

12

9.6

 

 

20

28

1.9

 

 

 

1-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

0400/0401

 

45

15

9.8

 

 

20

33

2.0

 

 

 

1-1/2"

 

 

 

 

 

 

 

 

 

 

 

 

 

0514

 

 

90

9

9

 

 

40

21

1.8

 

 

 

2"

 

 

 

 

 

 

 

 

 

 

 

 

 

0624

 

 

90

12

9.5

 

 

40

26

1.9

 

 

 

2"

 

 

 

 

 

 

 

 

 

 

 

 

 

0724

 

 

90

13

10

 

 

40

30

2.0

 

 

 

2"

 

 

 

 

 

 

 

 

 

 

 

 

 

0824

 

 

90

15

10.5

 

 

40

34

2.1

 

 

 

2"

 

 

 

 

 

 

 

 

 

 

 

 

 

0926

 

 

90

17

11

 

 

40

38

2.2

 

 

 

2 1/2"

 

 

 

200

8

9.7

 

90

17

2.1

 

3"

 

0962

 

 

90

18

11

 

 

40

39

2.2

 

 

 

2 1/2"

 

 

 

200

8

9.7

 

90

18

2.1

 

3"

 

1083

 

 

90

20

12

 

 

44

40

2.9

 

 

 

2 1/2"

 

 

 

200

9

10.3

 

90

20

2.3

 

3"

 

1125

 

 

90

20

12

 

 

46

40

3.1

 

 

 

2 1/2"

 

 

 

200

9

10.3

 

90

20

2.3

 

3"

 

1178

 

 

90

21

12.5

 

 

48

40

3.6

 

 

 

2 1/2"

 

 

 

200

10

11

 

90

21

2.4

 

3"

 

1223

 

 

90

22

12.5

 

 

50

40

3.9

 

 

 

2 1/2"

 

 

 

200

10

11

 

90

22

2.4

 

3"

 

1287

 

 

90

23

13.2

 

 

53

40

4.5

 

 

 

2 1/2"

 

 

 

200

11

11.7

 

90

23

2.5

 

3"

 

1336

 

 

90

24

13.2

 

 

55

40

4.9

 

 

 

2 1/2"

 

 

 

200

11

11.7

 

90

24

2.5

 

3"

 

1414

 

 

90

26

14

 

 

58

40

5.8

 

 

 

2 1/2"

 

 

 

200

12

12.2

 

90

26

2.7

 

3"

 

1468

 

 

90

27

14

 

 

60

40

6.2

 

 

 

2 1/2"

 

 

 

200

12

12.2

 

90

27

2.7

 

3"

 

1571

 

 

90

29

14.5

 

 

64

40

7.3

 

 

 

2 1/2"

 

 

 

200

13

13

 

90

29

2.8

 

3"

 

1631

 

 

90

30

14.5

 

 

67

40

8.1

 

 

 

2 1/2"

 

 

 

200

13

13

 

90

30

2.8

 

3"

 

1758

 

 

90

32

15.4

 

 

72

40

9.7

 

 

 

2 1/2"

 

 

 

200

14

14.7

 

90

32

3

 

3"

 

1826

 

 

90

33

15.4

 

 

75

40

10.6

 

 

 

2 1/2"

 

 

 

200

15

14.7

 

90

33

3

 

3"

 

2100

 

 

200

17

14.8

 

 

90

38

3.2

 

 

 

3"

 

 

 

400

9

18

 

180

19

4

 

4"

 

2500

 

 

200

20

15.8

 

 

102

40

4.3

 

 

 

3"

 

 

 

400

10

18.8

 

180

23

4.1

 

4"

 

3001

 

 

200

25

16.7

 

 

123

40

6.5

 

 

 

3"

 

 

 

400

12

19.5

 

180

27

4.3

 

4"

 

3500

 

 

200

29

17.5

 

 

144

40

9.3

 

 

 

3"

 

 

 

400

14

20.5

 

180

32

4.5

 

4"

4001

 

200

33

18.7

 

 

164

40

12.8

 

 

 

3"

 

 

400

16

21.5

 

180

36

4.7

4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GPM Flow rates limited by maximum acceptable velocity through heat exchanger tubes. May be increased by 10% for closed heating sys- tems.

* 4 Pass Heat Exchanger

BOLD TYPE indicates Low NOx models.

Table H: Maximum and Minimum Flow Rates

22

Page 22
Image 22
Raypak 1334001 operating instructions Maximum and Minimum Flow Rates