Models 0181-0401 and 0182-0400

Vent Terminal/Indoor Stack

Installation

1.Remove the louvered jacket top by removing four

(4) #10 flathead screws.

2.If originally installed, remove "Pagoda" top from the louvered jacket top.

3.Place the inner stack adapter panel over the flue collector inside the heater. Make sure the flanged side of the flue opening is up.

4.Turn the stack (drafthood) upside down and set it down bottom side up.

5.Turn the jacket top panel (removed in step 1) upside down and place it over the stack.

6.Attach the three (3) mounting brackets to the stack using the screws provided and the holes that are pre-drilled in the stack. Make sure the brackets are positioned with the flange near the top side of the stack (see Fig. 10). Caution must be taken not to over tighten and strip the screw threads.

7.Turn the assembled stack and jacket top, right side up. The jacket top will be trapped between the brackets and the top of the stack. Place the stack over the inner adapter panel flanged hole and lower the louvered jacket top panel back into its original position. Reinstall the four (4) green #10 flathead screws removed in step 1 above.

Models 0514-0824

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

Fig. 11: Indoor Top Installation

Models 0962-1826

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

SCREW HOLE LOCATION

3-1/4"

DRAFTHOOD

JACKET TOP PANEL

(part of the heater)

#10 SHEET METAL SCREW (3) MOUNTING BRACKET (3)

INNER STACK ADAPTER PANEL

FLUE COLLECTOR

(part of heater)

COMBUSTIBLE FLOOR SHIELD

(optional for indoor)

2-1/2"

Fig. 12: Indoor Top Installation

Models 2100-4001

These models have built-in drafthoods. For proper operation, the drafthood outlet must be connected to the venting system.

Fig. 10: Indoor Top Installation