Raypak 1334001 Start-Up Procedures, before Start-Up, General, Initial Start-Up- Pump and Motor

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 30
Image 30
START-UP

Location of Controls

START-UP

PROCEDURES

before Start-Up

Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the heater when the heater underwent tests speci- fied in the latest edition of the ANSI Z21.10.3/CSA 4.3 Standard.

General

Before lighting up a new installation, water should be flowing through the heater. Water pressure regulator should be set to minimum 25 PSI.

CAUTION: Propane gas is heavier than air and sinks to the ground. Exercise extreme care in light- ing heater in confined areas.

Initial Start-Up - Pump and Motor

Many pumps are now direct-drive. They have no cou- pler or bearing assembly. These pumps do not require lubrication. Others require SAE-30 non-detergent oil to lubricate both the motor and the bearing assembly. Check pump motor for type before adding oil.

Clean dust and lint from pump and motor. Check pump coupler and tighten if necessary.

Flush system before putting into operation to ensure that foreign material does not damage pump seals.

CAUTION: Pump must be off to check oil in bearing assembly. Do not run pump without water in system.

30

Page 30
Image 30
Raypak 1334001 Start-Up Procedures, before Start-Up, General, Initial Start-Up- Pump and Motor, Location of Controls