Raypak 1334001 operating instructions Vent Damper, Installation

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 19
Image 19

 

HORIZONTAL INSTALLATION

 

 

 

FLOW >

 

NO

 

 

 

 

 

 

 

 

YES

YES

TO HEATER

D808

TO CHIMNEY

 

 

 

 

 

NO

 

VERTICAL

 

INSTALL VENT

 

INSTALLATION

 

 

 

DAMPER WITH

 

 

 

TO CHIMNEY

 

 

 

ACTUATOR TO

 

 

 

 

 

 

 

 

SIDES OF VENT

 

 

 

 

ONLY. DO NOT

 

 

 

D808

MOUNT ABOVE OR

 

 

 

BELOW VENT.

 

 

 

 

ACTUATOR MAY BE

 

 

 

 

INSTALLED IN ANY

 

 

 

TO HEATER

POSITION ON

 

 

 

 

VERTICAL PIPE.

 

Fig. 16: Installing Vent Damper

Vent Damper

For safe, efficient operation, the vent damper and all flue product carrying areas of the appliance must be checked annually, with particular attention given to deterioration from corrosion or other sources. Check vent damper operation as follows:

1.When the heater is off, check that the vent damper position indicator points to the closed position, Fig. 18.

Damper

Damper

Position

Position

Indicator

Indicator

 

 

 

D808

 

 

 

 

N.O.

N.C.

 

 

 

 

 

End

 

1K2

 

 

 

 

Switch

 

 

 

 

 

 

C.

 

 

1K1

 

 

 

 

 

 

 

 

 

 

Motor

 

 

 

 

 

 

 

 

R

 

 

1K3

 

 

 

 

 

 

 

 

1R

 

 

 

 

1

 

2

3

4

5

Black

Orange

Red

 

 

Yellow

Blue

 

 

 

 

 

 

Limit

 

 

 

Thermostat or

 

 

 

 

 

Controller

 

 

 

 

Dual Valve

 

 

 

 

Combination Gas

 

 

 

 

Control or

 

 

 

Transformer

 

Ignition System

 

 

 

Optional Limit

Location

L1

(Hot)

L2

1

DAMPER OPEN

DAMPER CLOSED

Fig. 18: Vent Damper position Indicator Showing Open

&Closed Positions

2.Turn the thermostat or controller up to call for heat and check that the vent damper indicator points to the open position, Fig. 18.

3.Turn the thermostat or controller down again and check that the vent damper position indicator returns to the closed position.

THE VENT DAMPER MUST BE INSPECTED AT

1Power supply provide disconnect means an overload protection as required.

Fig. 17: Vent Damper General Wiring Diagram

INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED. IF IMPROPERLY INSTALLED, A HAZ- ARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON MONOXIDE POISONING, COULD RESULT.

LEAST ONCE A YEAR BY A TRAINED, EXPERI- ENCED SERVICE TECHNICIAN. THE NAME OF THE PERSON WHO ORIGINALLY INSTALLED YOUR VENT DAMPER IS SHOWN ON THE INSTALLATION LABEL. DAMPER MUST BE IN THE OPEN POSI- TION WHEN HEATER MAIN BURNERS ARE OPERATING.

19

Page 19
Image 19
Raypak 1334001 operating instructions Vent Damper, Installation