Raypak 1334001 operating instructions Gas Pressure Regulator, Venting of Diaphragm Gas Components

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 21
Image 21
MAXIMUM EQUIVALENT PIPE LENGTH

MAXIMUM EQUIVALENT PIPE LENGTH

NATURAL GAS 1000 BTU/Cubic Foot

.60 SPECIFIC GRAVITY @ 0.5" W.C. PRESSURE DROP

PROPANE GAS 2500 BTU/Cubic Foot

1.53 SPECIFIC GRAVITY @ 0.6" W.C. PRESSURE DROP

1/2"

N P

3/4"

1"

1-1/4"

1-1/2"

2"

2-1/2"

3"

4"

N

P

N

P

N

P

N

P

N

P

N

P

N

P

N

P

0133

15

35

60

 

145

 

200

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*0182/0181

-

15

30

 

65

 

95

 

250

 

400

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

*0260/0261

-

10

20

 

40

 

60

 

140

 

250

 

560

 

 

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

*0330/0331

 

-

15

 

25

 

35

 

85

 

150

 

380

 

360

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

*0400/0401

 

-

-

 

15

 

25

 

60

 

100

 

260

 

250

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

0514

 

 

-

 

10

 

15

 

35

 

65

 

150

 

130

 

360

 

500

 

-

 

-

 

-

 

-

 

-

 

-

 

-

0624

 

 

-

 

-

 

10

 

25

 

45

 

100

 

95

 

250

 

340

 

-

 

-

 

-

 

-

 

-

 

-

 

-

0724

 

 

-

 

-

 

-

 

20

 

35

 

80

 

75

 

180

 

260

 

600

 

-

 

-

 

-

 

-

 

-

 

-

0824

 

 

-

 

-

 

-

 

15

 

25

 

60

 

55

 

130

 

185

 

480

 

500

 

-

 

-

 

-

 

-

 

-

0926/0962

 

 

-

 

-

 

-

 

15

 

20

 

45

 

45

 

110

 

150

 

360

 

400

 

-

 

-

 

-

 

-

 

-

1083/1125

 

 

-

 

-

 

-

 

10

 

15

 

35

 

35

 

80

 

120

 

300

 

300

 

-

 

-

 

-

 

-

 

-

1178/1223

 

 

-

 

-

 

-

 

-

 

-

 

25

 

25

 

60

 

85

 

220

 

200

 

-

 

-

 

-

 

-

 

-

1287/1336

 

 

-

 

-

 

-

 

-

 

-

 

25

 

20

 

55

 

75

 

180

 

170

 

325

 

560

 

-

 

-

 

-

1414/1468

 

 

-

 

-

 

-

 

-

 

-

 

20

 

15

 

45

 

65

 

150

 

165

 

300

 

500

 

-

 

-

 

-

1571/1631

 

 

-

 

-

 

-

 

-

 

-

 

15

 

15

 

35

 

50

 

120

 

125

 

250

 

400

 

-

 

-

 

-

1758/1826

 

 

-

 

-

 

-

 

-

 

-

 

15

 

10

 

30

 

40

 

100

 

100

 

225

 

340

 

-

 

-

 

-

2100

 

 

-

 

-

 

-

 

-

 

-

 

10

 

10

 

25

 

30

 

80

 

75

 

175

 

260

 

-

 

-

 

-

2500

 

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

15

 

20

 

55

 

55

 

135

 

160

 

400

 

600

 

-

3001

 

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

10

 

15

 

35

 

40

 

85

 

120

 

250

 

500

 

-

3500

 

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

10

 

30

 

30

 

45

 

80

 

200

 

400

 

600

4001

 

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

-

 

5

 

20

 

25

 

35

 

65

 

160

 

300

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Models 0181, 0261, 0331, and 0401 are Low NOx units and are not available in propane.

A minimum of 7" WC and a maximum of 10.5" WC upstream pressure under load, and no load conditions must be provided for natural gas or a minimum of 11" WC and a maximum of 13" for propane.

Pressure drops from the no load condition to the full load condition must be no more than 30% for proper operation.

Table G: Maximum Equivalent Pipe Lengths

Gas Pressure Regulator

The gas pressure regulator located in the gas valve is preset nominally at 4" WC for natural gas, and 11" WC for propane. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point, taken with a manometer, should be about 3.7" WC natural gas and 10.5" WC propane. Models 0181, 0261, 0331, and 0401 should be 3.9 WC natural gas. If an adjustment is needed, turn adjustment screw clockwise to increase pressure, or counter-clockwise to decrease pressure.

Venting of Diaphragm Gas

Components

Fig. 20: Bleed Line Connection

Gas train components that have diaphragms in their construction are supplied with a bleed line connection that must be connected to the outside atmosphere as required by the National Fuel Gas Code. Under NO circumstances shall bleed lines terminate in the gas utilization equipment flue or exhaust system.

21

Page 21
Image 21
Raypak 1334001 Gas Pressure Regulator, Venting of Diaphragm Gas Components, Maximum Equivalent Pipe Length