Heater | Floor Base |
Model | Part |
Number | Number |
0133 | 001749 |
0182/0181 | 058313 |
0260/0261 | 058314 |
0330/0331 | 058315 |
0400/0401 | 058316 |
0514 | 056199 |
0624 | 056200 |
0724 | 056201 |
0824 | 056202 |
0926* | 054597 |
1083* | 054598 |
1178* | 054599 |
1287* | 054600 |
1414* | 054601 |
1571* | 058378 |
1758* | 058379 |
0962 | 059233 |
1125 | 059234 |
1223 | 059235 |
1336 | 059236 |
1468 | 059237 |
1631 | 059238 |
1826 | 059239 |
*Models with factory installed floor shield as standard.
BOLD TYPE indicates Low NOx models.
Table B: Combustible Floorshield Ordering Information
Fig. 2: Alternate Method for Providing a Non-
Combustible Base
Clearances
Installation Clearances
(All Dimensions are in Inches)
|
|
| Heater Size |
|
| ||
| 0133 | 0181 to |
| 0514 to |
| 0926 to | 2100 to |
Location |
| 0401 |
| 0824 |
| 1826 | 4001 |
Floor |
|
| See Note 1 |
|
| ||
Front |
|
| See Note 2 |
|
| ||
Back | 12 | 12 |
| 12 |
| 24 | 24 |
Right | 6 | 12 |
| 6 |
| 24 | 24 |
Left | 12 | 12 |
| 18 |
| 24 | 24 |
*Vent | 6 | 6 |
| 6 |
| 6 | 6 |
Indoor Top | 42 | 39 |
| 36 |
| 24 | 24 |
Outdoor Top |
| Unobstructed |
| NA |
Note 1: Combustible floor shield is required when heater is to be installed on a combustible surface. (See ordering info.)
Note 2: Servicing Clearances: Provide at least 24" (Models 0133- 1826), 48" (Models
Table C: Clearances From Combustible Surfaces
|
|
|
| Heater Size |
| ||
|
| 0133 | 0181 to |
| 0514 to | 0926 to | 2100 to |
Description | Location |
| 0401 |
| 0824 | 1826 | 4001 |
a. | Back | 9 | 9 |
| 9 | 16 | 16 |
without ventilated air space. | Right | 5 | 9 |
| 5 | 16 | 16 |
| Left | 9 | 9 |
| 12 | 16 | 16 |
| Vent | 5 | 5 |
| 5 | 5 | 5 |
| Indoor Top | 43 | 39 |
| 36 | 24 | 24 |
| Outdoor Top |
|
| Unobstructed | NA | ||
b. 1/2 in. insulation board | Back | 6 | 6 |
| 6 | 12 | 12 |
over 1 in. glass fiber or | Right | 3 | 6 |
| 3 | 12 | 12 |
mineral wool batts. | Left | 6 | 6 |
| 9 | 12 | 12 |
| Vent | 3 | 3 |
| 3 | 3 | 3 |
| Indoor Top | 30 | 30 |
| 24 | 16 | 16 |
| Outdoor Top |
|
| Unobstructed | NA | ||
c. 0.024 sheet metal over 1 in. | Back | 4 | 4 |
| 4 | 8 | 8 |
glass fiber or mineral wool | Right | 3 | 4 |
| 3 | 8 | 8 |
batts reinforced with wire | Left | 4 | 4 |
| 6 | 8 | 8 |
on rear face with ventilated | Vent | 3 | 3 |
| 3 | 3 | 3 |
air space. | Indoor Top | 24 | 24 |
| 18 | 12 | 12 |
| Outdoor Top |
|
| Unobstructed | NA | ||
d. | Back | 6 | 6 |
| 6 | 8 | 8 |
with ventilated air space. | Right | 6 | 6 |
| 6 | 8 | 8 |
| Left | 6 | 6 |
| 6 | 8 | 8 |
| Vent | 6 | 6 |
| 6 | 6 | 6 |
| Indoor Top | 42 | 39 |
| 36 | 24 | 24 |
| Outdoor Top | NA |
| Unobstructed | NA | ||
e. 0.024 sheet metal with | Back | 4 | 4 |
| 4 | 8 | 8 |
ventilated air space. | Right | 2 | 4 |
| 2 | 8 | 8 |
| Left | 4 | 4 |
| 6 | 8 | 8 |
| Vent | 2 | 2 |
| 2 | 2 | 2 |
| Indoor Top | 24 | 24 |
| 18 | 12 | 12 |
| Outdoor Top |
|
| Unobstructed | NA | ||
f. 1/2 in. thick insulation | Back | 4 | 4 |
| 4 | 8 | 8 |
board with ventilated | Right | 3 | 4 |
| 3 | 8 | 8 |
air space. | Left | 4 | 4 |
| 6 | 8 | 8 |
| Vent | 3 | 3 |
| 3 | 3 | 3 |
| Indoor Top | 24 | 24 |
| 18 | 12 | 12 |
| Outdoor Top | NA |
| Unobstructed | NA | ||
g. 0.024 sheet metal with | Back | 4 | 4 |
| 4 | 8 | 8 |
ventilated air space over | Right | 3 | 4 |
| 3 | 8 | 8 |
0.024 sheet metal with | Left | 4 | 4 |
| 6 | 8 | 8 |
ventilated air space. | Vent | 3 | 3 |
| 3 | 3 | 3 |
| Indoor Top | 24 | 24 |
| 18 | 12 | 12 |
| Outdoor Top |
|
| Unobstructed | NA | ||
h. 1 in. glass fiber or mineral | Back | 4 | 4 |
| 4 | 8 | 8 |
wool batts sandwiched | Right | 3 | 4 |
| 3 | 8 | 8 |
between two sheets 0.024 | Left | 4 | 4 |
| 6 | 8 | 8 |
sheet metal with ventilated | Vent | 3 | 3 |
| 3 | 3 | 3 |
air space. | Indoor Top | 24 | 24 |
| 18 | 12 | 12 |
| Outdoor Top | NA |
| Unobstructed | NA |
Table D: Clearances to Protected Surfaces
8