Raypak 1334001 Installation Clearances, All Dimensions are in Inches, Heater, Floor Base

Models: 1334001

1 52
Download 52 pages 39.44 Kb
Page 8
Image 8
Heater

Heater

Floor Base

Model
Part
Number

Number

0133

001749

0182/0181

058313

0260/0261

058314

0330/0331

058315

0400/0401

058316

0514

056199

0624

056200

0724

056201

0824

056202

0926*

054597

1083*

054598

1178*

054599

1287*

054600

1414*

054601

1571*

058378

1758*

058379

0962

059233

1125

059234

1223

059235

1336

059236

1468

059237

1631

059238

1826

059239

*Models with factory installed floor shield as standard.

BOLD TYPE indicates Low NOx models.

Table B: Combustible Floorshield Ordering Information

Fig. 2: Alternate Method for Providing a Non-

Combustible Base

Clearances

Installation Clearances

(All Dimensions are in Inches)

 

 

 

Heater Size

 

 

 

0133

0181 to

 

0514 to

 

0926 to

2100 to

Location

 

0401

 

0824

 

1826

4001

Floor

 

 

See Note 1

 

 

Front

 

 

See Note 2

 

 

Back

12

12

 

12

 

24

24

Right

6

12

 

6

 

24

24

Left

12

12

 

18

 

24

24

*Vent

6

6

 

6

 

6

6

Indoor Top

42

39

 

36

 

24

24

Outdoor Top

 

Unobstructed

 

NA

Note 1: Combustible floor shield is required when heater is to be installed on a combustible surface. (See ordering info.)

Note 2: Servicing Clearances: Provide at least 24" (Models 0133- 1826), 48" (Models 2100-4001) in front of unit for removal & servicing of the Controls & Burner Tray. Provide at least 18" on side opposite water connections for deliming of Heat Exchanger Tubes. *Vent includes factory supplied drafthoods and does not include field supplied vent systems above the drafthood. On Models 2100-4001 drafthood is built into heater.

Table C: Clearances From Combustible Surfaces

 

 

 

 

Heater Size

 

 

 

0133

0181 to

 

0514 to

0926 to

2100 to

Description

Location

 

0401

 

0824

1826

4001

a. 3-1/2 in. thick masonry walls

Back

9

9

 

9

16

16

without ventilated air space.

Right

5

9

 

5

16

16

 

Left

9

9

 

12

16

16

 

Vent

5

5

 

5

5

5

 

Indoor Top

43

39

 

36

24

24

 

Outdoor Top

 

 

Unobstructed

NA

b. 1/2 in. insulation board

Back

6

6

 

6

12

12

over 1 in. glass fiber or

Right

3

6

 

3

12

12

mineral wool batts.

Left

6

6

 

9

12

12

 

Vent

3

3

 

3

3

3

 

Indoor Top

30

30

 

24

16

16

 

Outdoor Top

 

 

Unobstructed

NA

c. 0.024 sheet metal over 1 in.

Back

4

4

 

4

8

8

glass fiber or mineral wool

Right

3

4

 

3

8

8

batts reinforced with wire

Left

4

4

 

6

8

8

on rear face with ventilated

Vent

3

3

 

3

3

3

air space.

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

d. 3-1/2 in. thick masonry wall

Back

6

6

 

6

8

8

with ventilated air space.

Right

6

6

 

6

8

8

 

Left

6

6

 

6

8

8

 

Vent

6

6

 

6

6

6

 

Indoor Top

42

39

 

36

24

24

 

Outdoor Top

NA

 

Unobstructed

NA

e. 0.024 sheet metal with

Back

4

4

 

4

8

8

ventilated air space.

Right

2

4

 

2

8

8

 

Left

4

4

 

6

8

8

 

Vent

2

2

 

2

2

2

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

f. 1/2 in. thick insulation

Back

4

4

 

4

8

8

board with ventilated

Right

3

4

 

3

8

8

air space.

Left

4

4

 

6

8

8

 

Vent

3

3

 

3

3

3

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

NA

 

Unobstructed

NA

g. 0.024 sheet metal with

Back

4

4

 

4

8

8

ventilated air space over

Right

3

4

 

3

8

8

0.024 sheet metal with

Left

4

4

 

6

8

8

ventilated air space.

Vent

3

3

 

3

3

3

 

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

 

 

Unobstructed

NA

h. 1 in. glass fiber or mineral

Back

4

4

 

4

8

8

wool batts sandwiched

Right

3

4

 

3

8

8

between two sheets 0.024

Left

4

4

 

6

8

8

sheet metal with ventilated

Vent

3

3

 

3

3

3

air space.

Indoor Top

24

24

 

18

12

12

 

Outdoor Top

NA

 

Unobstructed

NA

Table D: Clearances to Protected Surfaces

8

Page 8
Image 8
Raypak 1334001 Installation Clearances, All Dimensions are in Inches, Heater, Floor Base, Model, Part, Number