SECTION C: Installation
Hydronic Heating
Pump Selection
In order to ensure proper performance of your heater system, you must install a
Feedwater Regulator
Raypak recommends that a feedwater regulator be in- stalled and set at 12 psi minimum pressure at the highest point of the system. Install a check valve or back flow device upstream of the regulator, with a manual
Piping
All high points should be vented. A heater installed above radiation level must be provided with a low wa- ter
The piping system of a hot water heater connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the heater water during the cooling cycle. It is highly recommended that the piping be insulated.
Air-Separation/Expansion Tank
All heaters should be equipped with a properly sized expansion tank and air separator fitting as shown in Fig. 9.
Fig. 9:
Three-Way Valves
Fig. 10: Single Heater -
See Fig. 14 and instructions on page 16 for adjusting the manual bypass.
Fig. 11: Dual Heaters (Reverse/Return) with Primary/Secondary Piping
Domestic Hot Water
When designing the water piping system for domestic hot water applications, water hardness should be con- sidered. Table G indicates the suggested flow rates for soft, medium and hard water. Water hardness is ex- pressed in grains per gallon.
14