Raypak 503-2003 manual UDB Fault History

Models: 503-2003

1 58
Download 58 pages 52.53 Kb
Page 52
Image 52
UDB Fault History

SECTION F: Troubleshooting

UDB Fault History

To view the fault codes in the UDB history file:

1.Press and hold the switch labeled “SW1” for 5 seconds to access the fault history. LED 17 will begin to flash when the history has been accessed. See Fig. 38 on page 37.

2.Press the switch labeled “SW2” to scroll through the recorded faults in history.

3.When a fault is being displayed, the corresponding LED will light AND LED 17 will flash at a rate that corresponds to the fault number.

4.The faults are recorded and displayed on a last in, first out basis. The last fault recorded will be the first fault displayed. There is no time or date stamp associated with these faults.

5.Continue to push “SW2” to view subsequent faults.

6.When the history of faults has been exhausted, pushing “SW2” again will roll the fault history over and it will start again.

7.To exit the fault history, press and hold “SW1” for 5 seconds, or wait for 4 minutes and the board will automatically exit the history mode (fault LEDs will go out).

To clear the fault history, press and hold both “SW1” and “SW2” for 5 seconds.

NOTE: Once the history has been cleared, it cannot be recovered.

50

Page 52
Image 52
Raypak 503-2003 manual UDB Fault History