![Outdoor Installations](/images/new-backgrounds/35624/3562421x1.webp)
SECTION C: Installation
Venting not shown for clarity. Heater must be vented
per instructions in this manual
Fig. 6: Minimum Clearances from Combustible Surfaces – Indoor and Outdoor Installations
When installed according to the listed minimum clear- ances from combustible construction, these heaters can still be serviced without removing permanent structural construction around the heater. However, for ease of servicing, we recommend a clearance of at least 24 in. in front, at least 24 in. on the rear and 10 in. above the top of the heater. This will allow the heater to be ser- viced in its installed location without movement or removal of the heater.
Service clearances less than the minimum may require removal of the heater to service either the heat ex- changer or the burner components. In either case, the heater must be installed in a manner that will enable
the heater to be serviced without removing any struc- ture around the heater.
Outdoor Installations
These heaters are
Heater | Min. Clearance | Recommended | |
from Combustible | Service | ||
Side | |||
Surfaces | Clearance | ||
| |||
Rear | 12” | 24” | |
|
|
| |
Right Side | 1” | 1” | |
|
|
| |
Left Side | 1” | 1” | |
Top | Unobstructed | Unobstructed | |
|
|
| |
Vent | 12” | 12” | |
Termination |
|
|
Table E: Clearances – Outdoor Installations
The combustion air intake terminal MUST be used for outdoor installations. The hood is shipped loose and installed on the rear of the heater at the jobsite.
Combustion and Ventilation Air
NOTICE: Use of the heater in construction areas where fine particulate matter, such as concrete or dry- wall dust, is present may result in damage to the burner that is not covered by the warranty. If operated in a construction environment, a clean source of combus- tion air must be provided directly to the heater.
Indoor Units
The heater must be supplied with sufficient quantities of
9