SECTION C: Installation
Fig. 24: Horizontal
CAUTION: This venting system requires the installa- tion of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system will void all warranties on this heater.
Installation
These installations utilize the
installed horizontally through the wall to the outdoors. Adequate combustion and ventilation air must be sup- plied to the equipment room in accordance with the NFGC (U.S.) or B149.1 (Canada).
The total length of the horizontal
•75’ of straight flue pipe
•65’ of straight flue pipe and one elbow
•55’ of straight flue pipe and two elbows
•45’ of straight pipe and three elbows
The vent cap is not considered in the overall length of the venting system.
The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:
1.The vent must be installed with a condensate drain located in proximity to the heater as directed by the vent manufacturer.
2.The vent must be installed with a slight upward slope of not less than 1/4 inch per foot of horizon- tal run to the vent terminal.
| Certified Vent | Vent Size | Horizontal | Combustion Air |
| Air Inlet | ||
Model | Vent Length (Ft)* | Intake Pipe | Max. Length (Ft) ** | |||||
| Material | (in.) |
|
| Material |
|
|
|
| Min. | Max. | 6”Ø | 8” Ø | 10” Ø | |||
|
|
| ||||||
503 |
|
|
|
|
|
|
|
|
|
| 6 |
|
|
| 45 | 100 | N/A |
753 |
|
|
|
| ||||
|
|
|
|
| Galvanized Steel, |
|
|
|
1003 |
|
|
|
|
|
|
| |
| Category IV |
|
|
| PVC, |
|
|
|
1253 |
| 0 | 75 |
|
|
| ||
| ABS, |
|
|
| ||||
1503 |
|
|
|
|
|
| ||
|
|
|
| CPVC | N/A | 45 | 85 | |
1753 |
| 8 |
|
|
| |||
|
|
|
|
|
|
| ||
2003 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Vent lengths are based on a lateral length of 2 ft. Refer to the latest edition of the NFGC for further details.
**Subtract 10 ft per elbow. Max. 4 elbows.
Table M: Category IV Horizontal Vent & Horizontal Direct Vent
26