SECTION C: Installation
BLACK CIRCUIT
BREAKER
WHITE
GREEN
GROUND
A B C
Fig. 17: Wiring Connections
Check the power source:
AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX BC = <1 VAC Maximum
Fig. 18:
Making the Electrical Connections
Refer to Fig.
1.Verify that circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.
2.NOTE: Current draw noted on rating plate does not include pump current.
3.Turn off all power to the heater. Verify that power has been turned off by testing with a
4.Observe proper wire colors while making electri- cal connections. Many electronic controls are polarity sensitive. Components damaged by im-
proper electrical installation are not covered by warranty.
5.Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.
6.Install heater controls, thermostats, or building management systems in accordance with the appli- cable manufacturers’ instructions.
7.Conduit should not be used as the earth ground.
NOTICE: A grounding electrode conductor shall be used to connect the equipment grounding conductors, the equipment enclosures, and the grounded service conductor to the grounding electrode.
Field Wiring Connection
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause im- proper and dangerous operation. Verify proper operation after servicing.
DANGER: SHOCK HAZARD
Make sure electrical power to the heater is discon- nected to avoid potential serious injury or damage to components.
Fig. 19: Wiring Location
20