SECTION C: Installation

system operation by means of three push buttons (Item, ▲,▼). Item advances the display, while ▲,▼are used in the adjust menu.

2 seconds, then the software version is displayed for 2 seconds. At the end of that 4 second period, the control enters the normal operating mode and “VIEW” is dis- played. Pressing the scroll button “scrolls” through the displayed values in the “VIEW” menu.

Fig. 27: Modulating Temperature Control

User Interface

All items displayed by the control are organized into two menus, the view menu and the adjust menu. The active menu is displayed in the upper right hand side of the display in the menu field. The default menu is the view menu.

When the modulating temperature control is powered

 

Fig. 28: Modulating Temperature Control Display

up, the control turns on all segments in the display for

 

 

 

 

 

 

 

 

 

 

Item

Modes

 

Default

Range

 

 

 

 

 

 

 

Boiler

 

Water Heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BOIL TARGET

1, 2

140 ºF

 

---

OFF, 70 – 220 ºF

 

 

 

3

---

 

160 ºF

OFF, 70 – 200 ºF

 

 

 

4, 5

180 ºF

 

---

OFF, 70 – 220 ºF

 

 

 

 

 

 

 

 

 

 

BOIL MAX

1, 2, 4, 5, 6

200 ºF

 

---

120 – 225 ºF, OFF

 

 

 

3

---

 

180 ºF

120 – 200 ºF, OFF

 

 

 

 

 

 

 

 

 

 

BOIL MIN

1 - 5

135 ºF

 

135 ºF

OFF, 80 – 180 ºF

 

 

‘BURNER’ DELAY

1 - 5

1:30

 

1:30

0:00 to 3:00 Min.

 

 

 

 

 

 

 

 

 

 

BOIL MASS

1 - 5

1

 

1

1 (Low), 2 (Med), 3 (High)

 

 

 

 

 

 

 

 

 

 

DIFF

1 - 5

10 ºF

 

10 ºF

2 – 42 ºF

 

 

 

 

 

 

 

 

 

 

TANK TARGET

3

---

 

120 ºF

OFF, 70 – 190 ºF

 

 

TANK DIFF

3

---

 

5 ºF

2 – 10 ºF

 

 

 

 

 

 

 

 

 

 

PUMP DLY

All

3:00

 

3:00

OFF, 0:20 to 9:55 Min., ON

 

 

OUTDR START

4, 5

70 ºF

 

---

35 – 85 ºF

 

 

 

 

 

 

 

 

 

 

OUTDR DSGN

4, 5

-10 ºF

 

---

-40 – 32 ºF

 

 

 

 

 

 

 

 

 

 

BOIL START

4, 5

135 ºF

 

---

35 – 150 ºF

 

 

 

 

 

 

 

 

 

 

BOIL DSGN

4, 5

180 ºF

 

---

70 – 220 ºF

 

 

WWSD

4, 5

70 ºF

 

---

35 – 100 ºF, OFF

 

 

 

 

 

 

 

 

 

 

UNITS

All

ºF

 

ºF

ºF or ºC

 

 

MODE

---

2

 

3

1, 2, 3, 4, 5, 6

 

 

 

 

 

 

 

 

 

Table N: Modulating Temperature Control Default Setpoints

30

Page 32
Image 32