Image 51
SECTION F

Step 1

Step 2

Step 3

SECTION D: Start up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECTION F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Troubleshooting

Does the power switch provide

 

 

 

 

 

 

 

 

 

 

Check the switch and/or

 

 

 

 

 

NO

 

 

power to the control panel?

 

 

 

 

 

 

 

 

 

line voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there a Call For

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

NO

Unit is in standby mode.

 

 

 

 

 

 

 

 

Heat?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is Disable connection intact?

 

NO

 

 

 

 

Reattach.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check and correct power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does the combustion air

 

 

 

 

 

 

 

 

Is there 120VAC at the blower or

 

 

 

connections at main terminal

 

 

 

NO

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

blower relay?

 

 

block, circuit breaker panel or

blower come on?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blower relay.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Step 4

Is 4-20mA present at the quick disconnects on the black and blue wires of the temperature controller?

 

 

YES

YES

 

 

 

 

 

 

Does F2 on ignition module

have AC power?

Is 24VAC at the NC side of

NO

the air pressure switch?

 

 

 

 

YES

 

 

 

 

 

 

Is diagnostic board

 

 

 

 

 

 

 

 

 

 

NO

NO

 

 

 

 

indicating open

 

 

 

 

 

 

safeties?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

Is there continuity in the wire

NO

between F2 and Pin J5-6?

 

 

 

Is blower pressure setting

 

 

 

 

 

NO

 

 

(vacuum) correct?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace temperature

controller.

Correct Safety

NO

Repair or

 

Replace wire.

 

Correct the shutter

setting or blower

amp draw.

Step 5

Step 6

Is 24VAC at PS on ignition module?

Is connecting plug secure?

YES

Does igniter prove?

NO

 

 

YES

Replace air pressure switch.

NO

Correct wiring.

 

 

Is Amp draw during heat-

up for HSI greater than NOReplace HSI 3.1 Amps?

YES

Is air switch bouncing?

NO

 

YES

Step 7

Step 8

Step 9

 

Is the flame sensor signal to the

 

NO

 

 

Is gas pressure correct?

 

 

 

 

 

 

 

 

NO

 

ignition module greater than 1 uA DC?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is static and dynamic inlet gas

 

 

Correct the gas pressure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the unit running?

 

 

 

NO

 

 

 

 

pressure

 

correct?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace gas valve

YES

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The unit is okay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Call our Technical Service Department

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-800-927-2975 Outside California

1-800-627-2975 Inside California