Raypak 503-2003 manual SECTION E Operation, Lighting Instructions, To Turn Off Gas To Appliance

Models: 503-2003

1 58
Download 58 pages 52.53 Kb
Page 49
Image 49
Lighting Instructions

SECTION D: Start up

Lighting Instructions

1.Before lighting, make sure you have read all of the safety information in this manual.

2.Remove upper front panel.

3.Set the thermostat to the lowest setting.

4.Turn off all electrical power to the appliance.

5.This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.

6.Turn on main manual gas valve field installed near gas inlet connection on back of heater.

7.Wait 5 minutes to clear out any gas. Then smell for gas, especially near the floor. If you then smell gas, STOP! Follow the steps in the safety informa- tion on the front cover of this manual. If you do not smell gas, go to next step.

8.Turn on all electrical power to the appliance.

9.Set thermostat to desired setting. The appliance will operate. The igniter will glow after the pre- purge time delay (15 seconds). After igniter reaches temperature (30 seconds) the main valve should open. System will try for ignition one time (three times on optional 3-try ignition module). If flame is not sensed, lockout will commence.

10.If the appliance will not operate, follow the in- structions “To Turn Off Gas To Appliance,” and call your service technician or gas supplier.

11.Replace upper front panel.

SECTION E

Operation

12.If heater fails to start, verify the following:

a.There are no loose connections or that the ser- vice switch is off.

b.High temperature limit switch is set above wa- ter temperature or manual reset high limit is not tripped.

c.Thermostat is set above water temperature.

d.Gas is on at the meter and the heater.

e.Incoming dynamic gas pressure to the gas valve is NOT less than 4.0 in. WC for natural gas or propane gas.

To Turn Off Gas To Appliance

1.Shut off manual gas valve field installed near gas inlet connection on back of heater.

2.Remove upper front panel.

3.Set the thermostat to lowest setting.

4.Turn off all electrical power to the appliance if service is to be performed.

5.Replace access panel.

47

Page 49
Image 49
Raypak 503-2003 manual SECTION E Operation, Lighting Instructions, To Turn Off Gas To Appliance