INSTALLATION
945BG | 45O |
990 | 90O Elbow Galv. |
990B | 90O |
990G | 90O |
990BG | 90O |
991 | High Wind Term. Cap (Vertical) |
980 | Vertical Term. Cap |
982 | |
981 |
940Wall
941
3951 | Brass |
| Ceiling Support |
963Firestop Spacer
943Flashing
943S Flashing
953 | Storm Collar |
950 | Vinyl Siding Standoff |
988Wall Strap
942Wall Thimble
Parts not supplied by
Astro Cap (Australian)
DURA-FLUE
HORIZONTAL
INSTALLATIONS
1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the fluing system is attached. If this is the case, you may want to adjust the location of the unit.
2)Room Sealed pipe and fittings are designed with special
tory. Assemble the desired combination of pipe and el- bows to the appliance adaptor with pipe seams oriented to- wards the wall or ceil-
ing, as much out of view as possible. The
final positioning of the pipe and 90o elbow as- sembly is deter- mined by the mounting orien-
tation of the adaptor on the stove and twist- locked for a sol- id connection.
Note:
a)
pipe indentations so they match and slide in to the four entry slots on the male ends (diagram 1). Push the pipe sec- tions completely together, then twist- lock one section clockwise approxi- mately
Hint: Apply silicone to female end.
b)Horizontal runs of flue must be support- ed every three feet. Wall straps are available for this purpose.
3)With the pipe attached to the stove, slide the stove into its correct location, and mark the wall for a 10" x 10" / 254mm x 254mm (inside dimensions) square hole. The center of the square hole should line up with the center-
Diagram 1
line of the horizontal pipe, as shown in diagram2.Cutandframethe10inch(254mm) square hole in the exterior wall where the flue will be terminated. If the wall being penetrated is constructed of
Note:
a)The horizontal run of flue should have a 1/4 inch (6mm) rise for every 1 foot (.3m) of run towards the termination. Never allow the flue to run downward. This could cause high temperatures and may present the possibility of a fire.
Diagram 2
FG39:
b)The location of the horizontal flue ter- mination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Flue Termination Loca- tions, see diagram on page 8.
4)If installing the flue termination to a wall with vinyl siding, the Vinyl Siding Standoff must be used. Attach the Vinyl Siding Standoff to the Horizontal Flue Termination, but first run a bead of
Diagram 5
Note: If installing termination on a siding cov- ered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding. The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
5)Before connecting the horizontal run of flue pipe to the flue termination, slide the black decorative wall thimble cover over the flue pipe, then slide the Wall Thimble (Part # 942) over the flue pipe.
6)Slide the appliance and flue assembly to- wards the wall carefully inserting the flue pipe into the flue cap assembly. It is impor- tant that the flue pipe extends into the flue cap a sufficient distance so as to result in a minimum pipe overlap of
Regency FG39 FireGenie Freestanding Gas Stove | 13 |