Unit

INSTALLATION

 

 

 

 

 

 

 

 

TABLE 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Required Firestop, Radiation Shield, Or Attic Insulation Shield

 

 

 

 

 

 

Model

 

 

 

1st Floor

 

 

 

2nd Floor into Attic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CF Sentinal

 

 

 

Intermediate Joist Shield

 

 

 

Attic Insulation Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Super Pro 2100+

 

 

 

Attic Insulation Shield

 

 

 

Attic Insulation Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Super Vent 2100+

 

 

 

Attic Insulation Shield

 

 

 

Attic Insulation Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Security S2100+

 

 

Radiation Shield Fire Stop

 

Insulation Radiation Shield Attic Radiation Shield

 

 

Oliver Macleod Project HT6000+

 

Radiation Shield Fire Stop

 

Insulated Attic Radiation Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Simpson DuraPlus HTC

 

Fire Stop Radiation Shield

 

 

 

Attic Insulation Shield

 

 

 

 

ICC Excel 2100

 

 

 

Radiation Shield

 

Radiation Shield with Storm Collar

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Recommended Flue Height In Feet

 

 

 

 

 

 

 

 

 

(Measured from the top of the solid fuel appliance)

 

 

 

 

 

ELEVATION (FT)

 

 

 

 

 

 

# OF ELBOWS

 

 

 

 

 

 

ABOVE SEA LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

2 x 15o

4 x 15o

 

2 x 30o

 

4 x 30o

2 x 45o

 

4 x 45o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0ft - 1000ft

 

12.00ft

 

13.00ft

14.00ft

 

15.0ft

 

18.00ft

16.00ft

 

20.0ft

 

 

(0m - 305m)

 

(3.66m)

 

(3.96m)

(4.27m)

 

(4.57m)

 

(5.49m)

(4.88m)

 

(6.10m)

 

 

1000ft - 2000ft

 

12.48ft

 

13.52ft

14.56ft

 

15.6ft

 

18.72ft

16.64ft

 

20.0ft

 

 

(305m

- 610m)

 

(3.80m)

 

(4.12m)

(4.44m)

 

(4.75m)

 

(5.71m)

(5.07m)

 

(6.10m)

 

 

2000ft

- 3000ft

 

12.96ft

 

14.04ft

15.12ft

 

16.2ft

 

19.44ft

17.28ft

 

21.6ft

 

 

(610m

- 914m)

 

(3.95m)

 

(4.28m)

(4.61m)

 

(4.94m)

 

(5.93m)

(5.27m)

 

(6.58m)

 

 

3000ft

- 4000ft

 

13.44ft

 

14.56ft

15.68ft

 

16.8ft

 

20.16ft

17.92ft

 

22.4ft

 

 

(914m - 1219m)

 

(4.10m)

 

(4.44m)

(4.78m)

 

(5.12m)

 

(6.14m)

(5.46m)

 

(6.83m)

 

 

4000ft - 5000ft

 

13.92ft

 

15.08ft

16.24ft

 

17.4ft

 

20.88ft

18.56ft

 

23.2ft

 

 

(1219m

- 1524m)

 

(4.24m)

 

(4.60m)

(4.95m)

 

(5.30m)

 

(6.36m)

(5.66m)

 

(7.07m)

 

 

5000ft

- 6000ft

 

14.40ft

 

15.60ft

16.80ft

 

18.0ft

 

21.60ft

19.20ft

 

24.0ft

 

 

(1524m

- 1829m)

 

(4.39m)

 

(4.75m)

(5.12m)

 

(5.49m)

 

(6.58m)

(5.85m)

 

(7.32m)

 

 

6000ft

- 7000ft

 

14.88ft

 

16.12ft

17.36ft

 

18.6ft

 

22.32ft

19.84ft

 

24.8ft

 

 

(1829m

- 2134m)

 

(4.54m)

 

(4.91m)

(5.29m)

 

(5.67m)

 

(6.80m)

(6.05m)

 

(7.56m)

 

 

7000ft

- 8000ft

 

15.36ft

 

16.64ft

17.92ft

 

19.2ft

 

23.04ft

20.48ft

 

25.6ft

 

 

(2134m

- 2438m)

 

(4.68m)

 

(5.07m)

(5.46m)

 

(5.85m)

 

(7.02m)

(6.24m)

 

(7.80m)

 

 

8000ft

- 9000ft

 

15.84ft

 

17.16ft

18.48ft

 

19.8ft

 

23.76ft

21.12ft

 

26.4ft

 

 

(2438m

- 2743m)

 

(4.83m)

 

(5.23m)

(5.63m)

 

(6.04m)

 

(7.24m)

(6.44m)

 

(8.05m)

 

 

9000ft - 10000ft

 

16.32ft

 

17.68ft

19.04ft

 

20.4ft

 

24.48ft

21.76ft

 

27.2ft

 

 

(2743m

- 3048m)

 

(4.97m)

 

(5.39m)

(5.80m)

 

(6.22m)

 

(7.46m)

(6.63m)

 

(8.29m)

 

INSTALLATION

INSTALLING THE

OUTSIDE AIR KIT

Combustion air is fed to the fi rebox through a connection on the rear lower left side of the unit. A free fl owing supply of air must be available to this opening at all times. Combustion air may be taken from inside the building if the local building code allows, but performance may suffer. Also, it must go through the 6" (152mm) duct to the connection on the left hand side.

Air drawn from the interior of the building will affect the performance of gas or oil furnaces, and exhaust fans and fan driven appliances. This may cause a negative pressure in the house allowing smoke to back into the home.

The preferred source of combustion air is from outside the building. If possible, install the kit on the wind loading side of the building not the leeward or (negative pressure) side.

Note: Do not obtain combustion air from attic, garage or other enclosed space.

1)Put the supplied insulated air duct to a nearby exterior wall. Maximum length of duct is 20ft (6.1m). Duct length should be kept to a minimum and as straight as possible. Note: 4 ft. only is supplied with unit. Termination should be in an area with good air fl ow.

2)Ensure that your air source is not close to automobile exhaust, gas meters or other vents.

3)Cut a 7" (178mm) hole through the wall and mount the outside air kit.

4)Attach the two ends of the duct (making sure not to damage the insulating cover) after installing the fl ange on the fi replace side. Duct must be secured by screws or

clamp.Side￿Connection

Exterior

Wall

Outside

Metal

Insulated￿Metal

Vent

6” Duct

Outside Air Inlet must be 6 ft. (152mm) below

the chimney termination point

FPI FP90 Wood Fireplace

15

Page 15
Image 15
Regency FP90 installation manual Installing Outside AIR KIT, Elevation FT # of Elbows Above SEA Level