Regency FP90 Minimum Framing Clearances, Installation, Minimum Duct Clearances, B All Models

Models: FP90

1 40
Download 40 pages 7.42 Kb
Page 32
Image 32
MINIMUM FRAMING

HEATWAVE KIT (NOT EPA APPROVED)

MINIMUM FRAMING

CLEARANCES

*Wall studs must be 16" on center for mounting fan housing.

*Fan Housing: Maintain a 1/4" (6mm) clearance from fan housing to combustible material.

*Wall Registers must be 4"(102mm) from fl oor above or ceiling below.

INSTALLATION

NOTE: Installation of Heat Wave duct kit should be done prior to drywall installation.

A) R90 / EX90 Models:

1)Remove the cover plate from the fi replace side and discard.

B) All Models:

1)Determine the location of the air register/fan housing assembly. Cut a 5" x 16" (121mm x 406mm) hole between framing members (wall studs or fl oor joists). Maintain a 1/4" (6mm) clearance from fan housing to combustible material. See Framing Clearances section.

2)Mount and secure the fan housing assembly to framing members, the front of the fan housing will protrude 1/2" (51mm) out of the wall so it may be fi nished with drywall, etc. See diagram 2 below.

HEATWAVE KIT

Minimum Duct Clearances

The air duct has a '0' clearance to combustible. The fi rst 60" of pipe from the unit must be covered with insulation. (Insulation included with kit.)

Remove the 2 screws holding the cover plate

on the fi replace side.

2)Remove the knock-out and bend the tabs outward.

Center Round Duct collar over hole and attach to the tabs using 3 screws

NOTE: This must be done prior to placing fireplace into final position.

Diagram 1:

Front View

Diagram 2: Side View - Secure fan housing

to minimum 2 x 4 framing.

3)Install the air duct run. Secure the duct to the duct collar on the unit and to the fan housing with 3 screws (per end) and aluminum duct tape (UL 181A-P or equivalent).

The first 60" of duct pipe (from the unit) must be covered with insulation.

Round Air Duct: Attach the 6" round air duct (supplied) to the fireplace collar and run the duct to the fan housing. Attach the round-to-oval adaptor to the fan housing and the air duct to the adaptor.

32

FPI FP90 Wood Fireplace

Page 32
Image 32
Regency FP90 Minimum Framing Clearances, Installation, Minimum Duct Clearances, A R90 / EX90 Models, B All Models