Regency IG34-NG, IG34-ULPG, IG34-LPG Flue Liner Installation, GAS Pipe Pressure Testing

Models: IG34-LPG IG34-NG IG34-ULPG

1 32
Download 32 pages 29.38 Kb
Page 7
Image 7

INSTALLATION

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

FLUE LINER

INSTALLATION

1)Cut the flex liner as required.

2)Mark the end of one liner to indicate Inlet.

3)Connect the other end of the above liner to the inlet side of the termination adaptor, seal connection with high temperature silicone. Secure with gear clamp.

4)Connect the 2nd liner to the exhaust side of the adaptor, seal connection with high temperature silicone. Secure with gear clamp.

Be careful not to damage thermal insula- tion when sliding on vent connector plate.

This could cause blockage.

9)Connect the 2nd liner to the exhaust collar marked with an "E", seal connection with high temperature silicone. Secure with gear clamp.

4)Seal and or check the pilot outlet (# 8)

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.

6)When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver. Screw should be snug, but do not over tighten.

S.I.T. Valve Description

1)On-Off Solenoid Valve EV1

2)On-Off Solenoid Valve EV2

3)Inlet Pressure Test Point

4)Outlet Pressure Test Point

5)Connection for Pressure Regulator/ Combustion Chamber Compensation

6)Pressure Regulator for Minimum and Maximum Outlet Pressure

7)Gas Outlet Pressure Electric Modulator

8)Pilot Outlet

9)Main Gas Outlet

10)Side Outlet

5)Install flashing.

6)Insert both liners into chimney, passing through the damper opening.

7)Install termination cap.

8)Connect the marked end of the liner to the inlet collar of the vent connector plate marked with an "I", seal connection with high temperature silicone. Secure with gear clamp.

Install to AS5601 (Australia) /

NZS 5262 (New Zealand)

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 3.45 kPa (14" w.c.).

The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" (# 3) and/or "OUT" (# 4) pressure tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" (8mm) ID hose.

Regency IG34 Gas Inbuilt Fireplace

7

Page 7
Image 7
Regency IG34-NG, IG34-ULPG, IG34-LPG installation manual Flue Liner Installation, GAS Pipe Pressure Testing