REQUIREMENTS

MA Code - CO Detector

(for the State of Massachusetts only)

5.08: Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:

1.The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2.The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

Regency® L900 Direct Vent Gas Fireplace

5

INSTALLATION

Page 5
Image 5
Regency L900-NG, L900-LP installation manual Requirements, MA Code CO Detector

L900-LP, L900-NG specifications

The Regency L900-NG and L900-LP are remarkable gas fireplaces that epitomize both elegance and efficiency, bringing a blend of modern technology and traditional aesthetics to any living space. Designed for versatility, these units are suitable for homes with natural gas (NG) or propane (LP) gas lines, thus catering to a wide range of customer preferences.

One of the standout features of the L900 series is its impressive heating capacity. With up to 30,000 BTUs, these fireplaces can efficiently warm large areas, making them an exceptional choice for both residential and commercial settings. Their exceptional airflow and heat distribution ensure that users enjoy a cozy ambience throughout the space.

The L900 models are integrated with cutting-edge technology that enhances user experience. The advanced electronic ignition ensures reliable start-ups, while the variable flame height adjustment provides flexibility, allowing users to customize the heat output according to their needs. The inclusion of an optional remote control system adds an extra layer of convenience, enabling homeowners to operate the fireplace from anywhere in the room.

Aesthetic appeal is also a major highlight of the Regency L900 series. The full-view glass front maximizes the viewing area, allowing users to enjoy the mesmerizing flames fully. The sleek, contemporary design can easily complement various interior styles, from modern to traditional settings. Moreover, with several customizable options, including media choices such as glass, pebbles, or logs, users can personalize their fireplace to suit their decor.

Safety is always a priority with Regency products. The L900 models come equipped with a safety shut-off valve that activates in case of any irregularities, providing peace of mind for users. Additionally, the fireplace’s direct venting system ensures that combustion gases are safely expelled outside, allowing for effective ventilation without compromising indoor air quality.

Durability is another significant characteristic of the Regency L900 series. Constructed from high-quality materials, these fireplaces promise longevity and resilience, ensuring they can withstand the test of time.

Overall, the Regency L900-NG and L900-LP gas fireplaces stand out for their combination of performance, efficiency, and style. With their advanced features, customizable options, and focus on safety, they provide an enticing heating solution for any home or business, merging warmth with a touch of elegance.