SECTION 10: OUTSIDE AIR SUPPLY |
| |
The | blower motor has a pressure switch interlock that | |
outside air system. Halogenated hydrocarbons or | must be used. Wire this switch in series with the | |
other corrosive chemicals in the air can be drawn into | pump pressure switch. When using an outside air | |
the equipment and seriously damage the system | blower with a ROBERTS GORDON® System Control | |
components. Avoid the use of such chemical | or ROBERTS GORDON® ULTRAVAC™ control or | |
compounds near the air inlet to the heaters. | relay transformer, a separate load relay package is | |
IMPORTANT: If the building has a slight negative | required. Wire the control for the relay in parallel with | |
pressure or contaminants are present in the air, an | the pump. The outside air blower must have a | |
outside combustion air supply to the heaters is | separate 20A, 120V power supply. See Page 38, | |
strongly recommended. | Figure 21 for outside air blower internal wiring | |
All joints and seams in the air supply system must be | requirements. | |
airtight. Attach the filter housing to the burner | 10.2 | |
assembly using the wing nut provided. | ||
For a | ||
10.1 Pressurized | ||
single wall pipe duct may be attached to the burner | ||
See Page 39, Figure 23 for a typical layout of a | ||
and end vent. For length and duct sizing | ||
pressurized air supply system. | requirements, see duct design rules in Figure 19. To | |
For pressurized outside air supplies, the outside air | prevent condensation, insulate the outside air duct. | |
FIGURE 19: Duct Sizing |
| |
Outside Air System Design Requirements: |
|
Blower Performance (90707501):
112 Flow Units
One outside air blower is required per each
Duct Design Rules:
- System should be designed so that the blower is positioned closest to the highest flow requirements (end vents).
- When a duct is carrying more than 40 flow units, it must be at least 6" (15 cm) diameter.
Pressurized Systems
-6" (15 cm) diameter duct must not exceed 120' (36 m) total per system.
-4" (10 cm) diameter duct must not exceed 120'
(36 m) per radiant branch. Non Pressurized
-6" (15 cm) diameter duct must not exceed 90' (27 m) maximum 100 flow units
-4" (10 cm) diameter duct must not exceed 90' (27 m)
-Elbows are equivalent to 10' (3 m) of duct length.
37