Start with the main gas valve closed and the electric power off.

13.1 Checking the Gas Line

1.Open the main valve and verify that no gas is flowing through the meter.

2.Purge the line if this was not done following pressure testing with air.

3.Verify that the gas pressure is not above 14'' w.c. (1/2 PSIG).

4.Close the main gas valve.

13.2Checking the Electrical System

1.See that all temperature setpoints are set below room temperature.

2.Turn on power supply to system controls.

3.Check to see that no part of the system (i.e. burners, pump or air supply blower) is powered.

4.Individually check each zone by raising the zone temperature set points separately. Raising each zone temperature set point above room temperature should start the pump immediately. After a 45 second delay, the burners will begin their ignition sequence by sparking at the electrode (visible through the burner window).

5.Make a preliminary vacuum check at burners in branches that have an adjustable damper coupling. See Page 50, Figure 35 for manome- ter hookup to check vacuum. This check is to insure that all dampers are open before the system is fired. Vacuum, as measured at the end vents, should be approximately 3.5'' w.c. or slightly above (cold).

13.3Starting the System

NOTE: During the initial firing, the protective oil on the tubing may smoke for 30 to 60 minutes and adequate ventilation should be provided.

1.Start with all temperature setpoints below room temperature.

2.Open main gas valve.

3.Turn up temperature setpoints one zone at a time, waiting to see that all burners in a zone start. When the burner ignites, a blue flame will be observed through the viewer window.

4.If any abnormal operation occurs, see the trou- bleshooting section of the service instructions.

13.4Setting the Vacuum

1.Set temperature setpoints above room tempera- ture. See that all burners are operating properly.

2.Allow at least ½ hour operation for temperature to normalize, then check system vacuum bal- ance. Vacuum can be measured by inserting a manometer hose into the end vent as shown on Page 50, Figure 35. Normal end vent vacuum should be set at approximately 2.5'' w.c. to 3.0'' w.c. (hot).

Vacuum adjustments are made by means of the damper in the pump inlet and the adjustable damper coupling(s) in the system. Check the vacuum at all end vents and then adjust the damper coupling to obtain equal vacuum readings of 2.5'' w.c. to 3.0'' w.c. If end vent vacuum exceeds 3.0" w.c., adjust the pump inlet damper until vacuum readings are 2.5'' w.c. to 3.0'' w.c.

With systems designed to operate at maximum vacuum, it may not be possible to obtain vacuum differential readings at or slightly above 2.5'' w.c. If so, adjust the damper couplings to maximum but equal vacuum reading. Be sure to lock all dampers securely after adjustment.

3.Reset temperature setpoints to desired room temperature.

4.If heat is not required, turn off main switch and close the main gas valve.

49

Page 55
Image 55
Roberts Gorden CRV-B-4 Starting the System, Checking the Gas Line, Checking the Electrical System, Setting the Vacuum

CRV-B-4, CRV-B-12, CRV-B-2, CRV-B-10, CRV-B-6 specifications

The Roberts Gordon CRV-B-9 is a state-of-the-art infrared radiant heater designed for industrial and commercial heating applications. Renowned for its efficiency and effectiveness, the CRV-B-9 represents a significant advancement in the world of space heating solutions.

One of the main features of the CRV-B-9 is its advanced infrared technology, which allows for precise heating without the necessity of warming the entire space. This targeted heating provides immediate comfort, as it directly warms objects and people rather than the air around them, making it particularly effective in large warehouses, manufacturing facilities, and retail spaces.

The heater boasts an impressive output of up to 80,000 BTUs, making it suitable for a wide range of applications. It utilizes natural gas as fuel, which contributes to its efficiency and cost-effectiveness. With a robust design and durable construction, the CRV-B-9 is built to withstand the rigors of industrial environments while ensuring a long product lifespan.

Another significant characteristic of the CRV-B-9 is its ability to integrate with advanced control systems. This includes compatibility with programmable thermostats and energy management systems, allowing for optimized temperature control and reduced energy consumption. The heater can be adjusted to suit different operational needs, making it a flexible solution for various heating scenarios.

The CRV-B-9 also features a compact design, allowing for easy installation in a variety of spaces. Its low-profile shape and modular capability enable users to arrange multiple units to achieve the desired heating coverage without compromising floor space, a crucial aspect for busy, high-traffic areas.

Safety is a priority with the CRV-B-9, which is equipped with various safety features such as a flame safety cutoff switch and over-temperature protection. These mechanisms ensure safe operation, providing peace of mind for users in demanding environments.

In summary, the Roberts Gordon CRV-B-9 infrared radiant heater stands out for its innovative technology, impressive output, energy efficiency, and safety features. Its flexibility and robust design make it an ideal choice for businesses looking to enhance comfort while minimizing energy costs. Whether in a manufacturing plant or a retail outlet, the CRV-B-9 provides a reliable and effective heating solution.