Roberts Gorden CTHN-125, CTHN-200 Unitary Heater Requirements, Unitary Heater Design Requirements

Models: CTHN-60 CTHN-150 CTHN-175 CTHN-80 CTHN-125 CTHN-40 CTHN-100 CTHN-200

1 48
Download 48 pages 22.1 Kb
Page 19
Image 19

SECTION 8: UNITARY LINEAR & U-TUBE HEATER INSTALLATION

Deco Grille (1' x 8' [.3 m x 2.4 m])

01363003

Bracket

01365901

End Piece

01326801

Reinforcement

01365903

Joint Piece

91406700

1' x 8' (.3 m x 2.4 m) Protective Grille

 

Deco Grille (2' x 4' [.6 m x 1.2 m])

01365900

Shield Frame

01370408

Reflector Side Extension 8" x 48" (20 cm x 122 cm)

01370412

Reflector Side Extension 12" x 48" (30 cm x 122 cm)

01370416

Reflector Side Extension 16" x 48" (40 cm 122 cm)

91407000

Grille, Aluminum 2' x 4' (.6 m x 1.2 m)

 

Protective Grille

08050001

Grille, 40" (102 cm) Protective

08050002

Protective Grille End Cap

 

Fan and Pump Packages

05220000

Fan Package 40-150

05221000

Fan Package 175-200

02719105

EP-100 Pump Package

02719100

EP-100 Pump

02724700

Accessory Package

02716305

EP-201 Pump Package

01312001

EP-201 Pump

01317805

Accessory Package

02712034

EP-203 Pump Package

01312002

EP-203 Pump

01317805

Accessory Package

02723014

EP-301 Pump Package 4" (10 cm)

02730101

EP-301 Pump Assembly

02730104

Accessory Package

02723016

EP-301 Pump Package 6" (15 cm)

02730101

EP-301 Pump Assembly

02730106

Accessory Package

02723034

EP-303 Pump Package 4" (10 cm)

02730103

EP-303 Pump Assembly

02730104

Accessory Package

02723036

EP-303 Pump Package 6" (15 cm)

02730103

EP-303 Pump Assembly

02730106

Accessory Package

Pump Accessories

90430600K Pressure Switch

Starters and Contactors

10050001 Starter, 120 Vac for EP-203, 3 Ø

10050003 Starter, 120 Vac for EP-201, 1 Ø

10050008 Starter, 120 Vac for EP-301, 1 Ø

10050009 Contactor Package-

120 Vac Coil for EP-301, 230 V, 2 HP

10050010 Starter, 120 Vac for EP-303, 3 Ø

8.2 Unitary Heater Requirements

CTHN unitary heaters are typically shipped as a burner package, fan assembly and a tube and accessory package. The tube and accessory packages contain enough tube, reflector and hanging parts for one unitary CTHN heater. Elbows, u-tubes, controls, and any other parts must be purchased separately.

Table 5: Unitary Heater Design Requirements

See Page 14, Figure 13 for a general overview of a CTHN unitary heater. CTHN unitary heaters are controlled by thermostat.

Table 5 summarizes the design requirements for a CTHN unitary heater.

Burner Model:

CTHN-40

CTHN-60

CTHN-80

CTHN-100

CTHN-125

CTHN-150

CTHN-175

CTHN-200

Maximum Number of Burners Allowed

1

1

1

1

1

1

-

-

per Fan Assembly (P/N 05220000)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Number of Burners Allowed

-

-

-

-

-

-

1

1

per Fan Assembly (P/N 05221000)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Radiant Tube Length

10' (3 m)

20' (6 m)

20' (6 m)

30' (9 m)

40' (12 m)

40' (12 m)

50' (15 m)

50' (15 m)

 

 

 

 

 

 

 

 

 

Minimum Distance from Burner to Elbow or

10' (3 m)

10' (3 m)

10' (3 m)

15' (4.5 m)

15' (4.5 m)

20' (6 m)

20' (6 m)

20' (6 m)

U-Tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Page 19
Image 19
Roberts Gorden CTHN-125, CTHN-200, CTHN-100, CTHN-40, CTHN-80 Unitary Heater Requirements, Unitary Heater Design Requirements