Roberts Gorden CTHN-80, CTHN-200, CTHN-100 Multiburner Design Requirements, Burners Per Pump

Models: CTHN-60 CTHN-150 CTHN-175 CTHN-80 CTHN-125 CTHN-40 CTHN-100 CTHN-200

1 48
Download 48 pages 22.1 Kb
Page 36
Image 36
Table 10: Multiburner Design Requirements

CTHN-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

Table 10: Multiburner Design Requirements

Burner Model:

CTHN-40

CTHN-60

CTHN-80 CTHN-100 CTHN-125 CTHN-150

CTHN-175

CTHN-200

Radiant Tube Length

20' (6 m)

30' (9 m)

30' (9 m)

40' (12 m)

50' (15 m)

50' (15 m)

60' (18 m)

60' (18 m)

 

 

 

 

 

 

 

 

 

Minimum Manifold Tube Length per Burner

3' (1 m)

3' (1 m)

3' (1 m)

6' (2 m)

6' (2 m)

10' (3 m)

10' (3 m)

10' (3 m)

 

 

 

 

 

 

 

 

 

Maximum Manifold Tube Length per

30' (9 m)

35' (10.5 m)

40' (12 m)

45' (13.5 m)

50' (15 m)

55' (16.5 m)

60' (18 m)

60' (18 m)

Burner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Distance from Burner to Elbow

10' (3 m)

10' (3 m)

10' (3 m)

15' (4.5 m)

15' (4.5 m)

20' (6 m)

20' (6 m)

20' (6 m)

or U-tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Elbows Allowed per Burner*

2

2

2

2

2

2

2

2

 

 

 

 

 

 

 

 

 

* U-tube = 2 elbows

 

 

 

 

 

 

 

 

9.3 Burners Per Pump

1.The maximum number of burners per pump is shown in Table 11.

2.When combining different burner inputs in a system, the number of burners per pump (0' - 2,000' altitude) is given by the sum of their inputs:

a.EP-100 up to 500,000 Btu/h max, but not more than 4 burners.

b. EP-200 up to 750,000 Btu/h max, but not more than 6 burners.

c. EP-300 up to 1,600,000 Btu/h max, number of burners is limited to the maximum number of burners listed in Table 11 for the largest input model used.

Table 11: Number of Burners Allowed Per Pump

Pump Model

Altitude

CTHN-40

CTHN-60 CTHN-80

CTHN-100

CTHN-125 CTHN-150 CTHN-175 CTHN-200

 

0' - 2,000'

4

4

4

4

4

3

2

2

 

 

 

 

 

 

 

 

 

 

 

2,001' - 3,000'

4

4

4

4

3

3

2

2

 

 

 

 

 

 

 

 

 

 

 

3,001' - 4,000'

4

4

4

4

3

2

2

2

 

 

 

 

 

 

 

 

 

 

EP-100

4,001' - 5,000'

4

4

4

4

3

2

2

2

 

 

 

 

 

 

 

 

 

5,001' - 6,000'

4

4

4

4

3

2

2

2

 

 

 

 

 

 

 

 

 

 

 

 

6,001' - 7,000'

4

4

4

3

3

2

2

2

 

 

 

 

 

 

 

 

 

 

 

7,001' - 8,000'

4

4

4

3

3

2

2

1

 

 

 

 

 

 

 

 

 

 

 

8,001' - 9,000'

4

4

4

3

2

2

2

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0' - 2,000'

6

6

6

6

6

5

4

4

 

 

 

 

 

 

 

 

 

 

 

2,001' - 3,000'

6

6

6

6

6

5

4

3

 

 

 

 

 

 

 

 

 

 

 

3,001' - 4,000'

6

6

6

6

5

4

4

3

 

 

 

 

 

 

 

 

 

 

EP-200 Series

4,001' - 5,000'

6

6

6

6

5

4

4

3

 

 

 

 

 

 

 

 

 

5,001' - 6,000'

6

6

6

6

5

4

3

3

 

 

 

 

 

 

 

 

 

 

 

 

6,001' - 7,000'

6

6

6

6

5

4

3

3

 

 

 

 

 

 

 

 

 

 

 

7,001' - 8,000'

6

6

6

6

5

4

3

3

 

 

 

 

 

 

 

 

 

 

 

8,001' - 9,000'

6

6

6

6

5

4

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0' - 2,000'

16

16

14

12

12

10

8

8

 

 

 

 

 

 

 

 

 

 

 

2,001' - 3,000'

16

16

14

12

12

9

8

7

 

 

 

 

 

 

 

 

 

 

 

3,001' - 4,000'

16

16

14

12

11

9

8

7

 

 

 

 

 

 

 

 

 

 

EP-300 Series

4,001' - 5,000'

16

16

14

12

10

9

7

6

 

 

 

 

 

 

 

 

 

5,001' - 6,000'

16

16

14

12

10

8

7

6

 

 

 

 

 

 

 

 

 

 

 

 

6,001' - 7,000'

16

16

14

12

10

8

7

6

 

 

 

 

 

 

 

 

 

 

 

7,001' - 8,000'

16

16

14

12

10

8

6

6

 

 

 

 

 

 

 

 

 

 

 

8,001' - 9,000'

16

16

14

12

10

8

6

6

 

 

 

 

 

 

 

 

 

 

30

Page 36
Image 36
Roberts Gorden CTHN-80, CTHN-200 Multiburner Design Requirements, Burners Per Pump, Number of Burners Allowed Per Pump