Roberts Gorden TF-300, TF-350, TF-120, TF-200 ± 2 5 cm, 4.1 Coupling and Tube Assembly Continued

Models: TF-380 TF-250 TF-160 TF-200 TF-120 TF-300 TF-350

1 72
Download 72 pages 34.8 Kb
Page 29
Image 29
Step 7.4.1 Coupling and Tube Assembly (Continued)

SECTION 7: HEATER INSTALLATION

Step 7.4.1 Coupling and Tube Assembly (Continued)

Tighten slide bar as shown below

 

Drive slide bar until tight.

 

End of slide bar should be

 

within tolerance listed below.

 

± 2" (5 cm)

Correct slide bar

Incorrect slide bar

dimensions

 

position

Repeat Step 7.4 A - D until all tubes are assembled. See Page 23, Section 7.4.2.

Step 7.4.2 Coupling and Tube Assembly (Continued)

 

Minimum Tube Length

Model

Per Side

 

 

TF-120

20’ (6 m)

 

 

TF-160

20’ (6 m)

 

 

TF-200

30’ (9 m)

 

 

TF-250

40’ (12 m)

 

 

TF-300

50’ (15 m)

 

 

TF-350

50’ (15 m)

 

 

TF-380

60’ (18 m)

 

 

See recommended venting lengths on Page 37, Section 9, when using maximum tube lengths.

7' 6" ± 1'

(229 cm ± 25 cm)

10' Typ. ± 1'

(254 cm Typ ± 25 cm)

23

Page 29
Image 29
Roberts Gorden TF-300, TF-350 ± 2 5 cm, 4.1 Coupling and Tube Assembly Continued, 4.2 Coupling and Tube Assembly Continued