TROUBLESHOOT ENDS.

Yes

Does the

burner light?

No

Were the gas lines

No

purged of air?

 

 

Yes

Is the inlet gas pressure

during ignition correct? Yes (Natural 5.0" min.,

LP should be 12.0")

No

Check gas line stop cock.

Contact gas company.

No

 

 

Check for obstructions in

 

 

orifices and air plates

 

 

inside the burner.

 

 

Yes

 

 

Is the gas outlet pressure

Purge Lines.

 

3.5" for Natural Gas

 

 

(10.5" for LP)?

 

 

Yes

Measure voltage on valve

 

Is there gas outlet

terminals. Is there 24 V

Yes

pressure available during

during ignition time?

 

the ignition period?

No

 

No

Are the wires connecting

 

Is the knob on the gas valve

the ignition module OK?

 

in the ON position?

Yes

 

No

No

Adjust the

valve pressure.

 

Yes

Replace gas valve.

 

 

Replace/correct wires.

Yes

 

 

 

Does the burner

 

Are the wires

 

No

connecting the module

Yes

stay on?

 

and electrodes OK?

 

 

 

 

 

 

No

 

 

 

Replace/correct wires.

 

Yes

 

 

 

Does the burner turn off

 

Check the thermostat and

 

No

check the continuity of

 

when the call for heat

 

 

the ground wire.

 

ends?

 

 

 

 

 

Yes

 

 

 

TROUBLESHOOT ENDS.

 

Contact

 

If problems persist, contact

 

 

ROBERTS GORDON®

 

Roberts-Gordon LLC

 

Independent Distributor.

 

at www.rg-inc.com.

 

55

Replace ignition module.

Turn valve ON.

Replace ignition module.

 

SECTION 13: TROUBLESHOOTING