Roberts Gorden TF-120, TF-350, TF-300, TF-200 Typical Suspension Details, Critical Hanger Placement

Models: TF-380 TF-250 TF-160 TF-200 TF-120 TF-300 TF-350

1 72
Download 72 pages 34.8 Kb
Page 23
Image 23
FIGURE 14: Critical Hanger Placement

SECTION 7: HEATER INSTALLATION

FIGURE 14: Critical Hanger Placement

Typical Suspension Details

 

Beam Clamp

 

 

 

Anchor

 

 

Screw Hook

 

 

3/8"

 

 

Chain Size

 

Rod 3/8"

3/16"

24" min.*

Minimum

 

 

(61 cm)

“X”*

 

 

 

 

 

S-hooks

Concrete Beam Locknut Wood Beam

Washers Typical Suspension Details

Turnbuckle

* Allows for thermal expansion of system

Not Included

S-hooks

 

 

 

 

Side View

 

 

 

Hanger

Hanger

 

 

 

 

Reflector

 

 

 

 

Must Be Within 4" (10 cm)

Front View

 

45° Angle

Total Straight Length (both sides) or Length from U-Tube to U-Tube

Typical Expansion

Minimum “X” Length

in a Double "U" Layout

 

Each Side

 

 

 

 

0’ - 50’

 

±1” (3 cm)

 

12” (31 cm)

51’ - 60’

 

±2” (5 cm)

 

18” (46 cm)

61’ - 80’

 

±3” (8 cm)

 

24” (61 cm)

81’ - 100’

 

±4” (10 cm)

 

30" (76 cm)

101’ - 120’

 

±5” (13 cm)

 

36" (91 cm)

121’ - 140’

 

±6” (15 cm)

 

42" (107 cm)

141’ - 160’

 

±7” (18 cm)

 

48" (122 cm)

If the installation requires a shorter suspension length than the minimum listed, the suspension length may be reduced by 6" (16 cm). In this case, tube clamps MUST be used at the two farthest hangers on each side of the burner. See Page 18, Figure 15.

Description

Part Number

S-Hook

91907302

 

 

Tube/Reflector Hanger

03090100

 

 

17

Page 23
Image 23
Roberts Gorden TF-120, TF-350, TF-300, TF-200, TF-160, TF-250, TF-380 Typical Suspension Details, Critical Hanger Placement