SECTION 5: MAJOR COMPONENTS 5.1 General

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 5: MAJOR COMPONENTS 5.1 General

Heaters are designed for installation above 6'

(1.8 m). These heaters must be installed within the heated space. Duct delivery systems are not permitted with axial fan units. When handling or supporting the heater from below, ensure that the weight is taken at the support points.

The gas or electrical supply lines must not be used to support the heater.

Do not locate the gas or electrical supply lines directly over the path of the flue products from the heater.

The heater must be installed in accordance with clearances to combustibles as indicated on the wall tag and this manual.

5.2 Shelf Mounting and Suspension

5.2 Shelf Mounting and Suspension WARNING

Crush Hazard

Use 3/8" threaded rod minimum.

Failure to follow these instructions can result in death, injury or property damage.

Four suspension points (3/8" nuts) are located on the top of the heater. Drop rods must be 3/8" diameter mild steel.

When handling or supporting the heater from below, ensure that the weight is taken at the support points. For typical suspension, See Page 11, Figure 5.

For typical shelf mounting on existing shelf, See Page 11, Figure 6

5.3 Wall Mounting

For typical suspension, See Page 12, Figure 7. Wall mounted heaters blowing parallel to the wall can only be installed with the service door away from the wall.

The wall mounting brackets must be attached to a suitable wall using all mounting holes. Screw sizes less than 3/8" may not be used. In order for the wall mounting brackets to adequately carry the weight of the heater, it must be installed according to best building practices.

10

Page 16
Image 16
Roberts Gorden UHA[X][S] 60, UHA[X][S] 45 MAJOR COMPONENTS 5.1 General, Shelf Mounting and Suspension, Wall Mounting