10.2.5 External Controls

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

Heat exchanger could be damaged. Warranty will not cover damage to the heat exchanger if operated improperly. Only use the disconnect switch for turning off heater for service or during off-season.

10.2.5 External Controls

External controls may include time switch, interlock switch, room thermostat and frost thermostat. Operate each control to ensure that they function correctly. Set the switches (if fitted) and thermostat(s) to the users’ requirements.

10.3 Complete Start-Up

Ensure that all covers are fitted correctly and all test points are properly sealed.

10.3.1 Instruction to the User

Explain the controls of the heater to the user including how to turn it on and off, using the controls fitted on site.

Give this manual to the user.

Ensure that the user is shown and understands the importance of maintaining clearances to combustibles on Page 7, Figure 4 and the user instructions on Page 6, Section 3 and Page 33, Section 11 and all warnings defined in this manual.

32

Page 38
Image 38
Roberts Gorden UHA[X][S] 125, UHA[X][S] 45, UHA[X][S] 30 External Controls, Complete Start-Up, Instruction to the User