Roberts Gorden UHA[X][S] 125, UHA[X][S] 45, UHA[X][S] 30 General Technical Data Table All Models

Models: UHA[X][S] 75 UHA[X][S] 60 UHA[X][S] 100 UHA[X][S] 125 UHA[X][S] 30 UHA[X][S] 45

1 62
Download 62 pages 51.32 Kb
Page 56
Image 56
15.2 General Technical Data Table (All Models)

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

15.2 General Technical Data Table (All Models)

 

Model

UHA[X][S]

UHA[X][S]4

UHA[X][S]

UHA[X][S]

UHA[X][S]

UHA[X][S]

 

30

5

60

75

100

125

 

 

 

 

 

 

 

 

 

 

Low Profile UHA[X][S] Axial Fans

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Full Load Amps @ 115 V

A

3.0

3.0

4.1

4.1

5.8

5.8

 

 

 

 

 

 

 

 

Air Volume

CFM

691

691

1376

1376

1902

1902

 

 

 

 

 

 

 

 

Flue and Air Intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flue and Air Intake Size

in (cm)

 

 

4 (10) - All Models

 

 

 

 

 

 

 

 

 

 

*Maximum Straight Flue/Air Intake

ft (m)

25 (7.6)

25 (7.6)

25 (7.6)

25 (12.2)

40 (12.2)

40 (12.2)

 

 

 

 

 

 

 

 

*Do not exceed the maximum length of flue stated or heater may not operate properly.

15.3 Technical Data Table (All Models)

 

Model

UHA[X][S]

UHA[X][S]

UHA[X][S]

UHA[X][S]

UHA[X][S]

UHA[X][S]

 

30

45

60

75

100

125

 

 

 

 

 

 

 

 

 

 

Total Input

(Btu/h) x (1000)

30

45

60

75

100

125

 

 

 

 

 

 

 

 

Total Output

(Btu/h) x (1000)

24.6

36.9

49.2

61.5

82

102.5

 

 

 

 

 

 

 

 

Efficiency

%

 

 

82 - All Models

 

 

 

 

 

 

 

 

 

 

Natural Gas (G20) Data - Inlet Pressure 5.0 in wc Min., 14 in wc Max.

Burner Pressure

in wc

3.7

3.6

3.7

3.5

2.6

3.3

LPG / Propane (G31) Data - Inlet Pressure 12.0 in wc Min., 14 in wc Max.

Burner Pressure

in wc

9.4

9.6

9.6

10.0

9.1

10.0