14.2 Burner Compartment

SECTION 14: REPLACEMENT PARTS

14.2 Burner Compartment

Burner

Compartment

14.2.1 Burner Injectors Cover

Viewing port for flame probe

Flame Probe

Ignition Electrode

The burner compartment is a sealed compartment. Following any work, re-seal the compartment with the gas pipe rubber seal fully in place and all screws fitted and tight.

Remove flexible

.

air duct from spigot

NOTE: Separated combustion

 

 

model shown.

Remove screws and

 

pull off burner cover

 

14.2.1 Burner Injectors

Inshot

Burners

Orifices Manual backgroundManual background

ManifoldManual background

Mounting

Bracket Grommet

Manifold

Remove manifold

screws and pull

out manifold

ManifoldManual background

Unscrew

Orifices

Marking

Folded

Hem

Ensure gas tight fitting of injectors.

Ensure correct alignment with burners.

Ensure all pipe joints are gas tight.

MODEL

UHA[X][S] 30

UHA[X][S] 45

UHA[X][S] 60

UHA[X][S] 75

UHA[X][S] 100

UHA[X][S] 125

 

 

 

 

 

 

 

Orifice Quantity

2

3

4

5

6

7

 

 

 

 

 

 

 

Natural Gas (G20)

 

 

 

 

 

 

 

 

 

 

 

 

 

Orifice Marking

49

49

49

49

46

46

 

 

 

 

 

 

 

P/N

91930049

91930049

91930049

91930049

91930046

91930046

 

 

 

 

 

 

 

Propane (G31)

 

 

 

 

 

 

 

 

 

 

 

 

 

Orifice Marking

56

56

56

1.15 mm

1.25 mm

1.25 mm

 

 

 

 

 

 

 

P/N

91930056

91930056

91930056

91930115

91930125

91930125

 

 

 

 

 

 

 

43

Page 49
Image 49
Roberts Gorden UHA[X][S] 30, UHA[X][S] 45, UHA[X][S] 125, UHA[X][S] 100, UHA[X][S] 60 Burner Compartment, Burner Injectors