SECTION 13: TROUBLESHOOTING 13.1 General

UHA LOW PROFILE UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 13: TROUBLESHOOTING 13.1 General

START

Are gas & electrical

No

Turn on supplies.

supplies on?

 

 

STARTWARNING

Explosion Hazard

Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Turn off gas and electrical supplies before performing service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

Yes

Is ignition control showing a

"4 flashes" LED code?

Noo

Is ignition control showing a

"2 flashes" LED code?

No

Does the flue

blower run?

 

UHA 30 - 75: Press in reset

 

button on manual reset limit

 

switch. UHA 100 - 125: Wait

Yes

10 - 15 minutes for limit Yes

 

switch to cool. Does fan

 

stop running?

 

No

 

Replace temperature

 

limit switch.

 

Burner has locked out due

Yes

to ignition failure. Use

Troubleshooting for

 

 

Automatic Ignition Burner

 

Systems section to test

 

burner.

No

Use Troubleshooting for

Flue Blower section to test

 

fan.

Fan and limit switch are operating normally.

Yess

With external controls (i.e.

 

Has burner “Locked Out”? No

thermostat) on, does the No

burner continue through the

 

 

heating cycle?

 

 

 

 

Yes

 

 

Use Troubleshooting for

 

 

Automatic Ignition Burner

 

 

Systems section to test burner.

Yes

 

 

Heater Operating

 

If problems persist, contact

No

Roberts-Gordon LLC at

TROUBLESHOOT ENDS.

www.rg-inc.com

 

The limit switch has

 

tripped. See Manual Reset No

Replace limit switch.

Limit Switch Figure.

 

Yes

Ensure proper air flow clearance for axial fan. Open louvers slightly.

Replace axial fan if it does

not operate.

38

Page 44
Image 44