Roberts Gorden UHA[X][S] 75 Servicing Instructions, Burner Maintenance, Gas Valve Maintenance

Models: UHA[X][S] 75 UHA[X][S] 60 UHA[X][S] 100 UHA[X][S] 125 UHA[X][S] 30 UHA[X][S] 45

1 62
Download 62 pages 51.32 Kb
Page 41
Image 41
SECTION 12: SERVICING

SECTION 12: SERVICING

SECTION 12: SERVICING

12.1 Servicing InstructionsWARNING

Explosion Hazard

Installation, service and annual inspection must be done by a contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Turn off gas and electrical supplies before performing service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

12.1 Servicing Instructions

After start-up, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be required.

IMPORTANT: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions on Page 29, Section 10 through Page 32, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 38, Section 13 through Page 41, Section 13.5.

IMPORTANT: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.

IMPORTANT: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free

12.2 Burner Maintenance

1.Open the door and remove the burner compartment cover. See Page 43, Section 14.2.

2.Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 43, Section 14.2.

3.Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as required.

12.3 Fan/Motor Assembly Maintenance

12.2 Burner Maintenance WARNING

Cut Hazard

Turn off gas and electrical supply before maintenance.

Fan can start automatically at any time.

Failure to follow these instructions can result in severe injury or product damage.

The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.

12.4 Heat Exchanger Maintenance

The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.

12.5 Gas Valve Maintenance

No regular maintenance is required on this device. To change gas control valves, See Page 42, Section

14.1.

Do not repair or disassemble gas valve.

Replace faulty gas valves with replacement parts sold and supplied by Roberts-Gordon.

12.6 Flue Blower

The flue blower should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 46, Section 14.6). Ensure that the fan is free to run and that the fan wheel is clean.

35

Page 41
Image 41
Roberts Gorden UHA[X][S] 75 Servicing Instructions, Burner Maintenance, 12.3 Fan/Motor Assembly Maintenance