Roberts Gorden UHA[X][S] 125 Fire Hazard, close to heater, injury or property damage, Models 150

Models: UHA[X][S] 75 UHA[X][S] 60 UHA[X][S] 100 UHA[X][S] 125 UHA[X][S] 30 UHA[X][S] 45

1 62
Download 62 pages 51.32 Kb
Page 62
Image 62
OPERATING INSTRUCTIONS

Attach this information to the wall near the ROBERTS GORDON® heater

®

Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.

OPERATING INSTRUCTIONS

WARNING

 

 

 

1.STOP! Read all safety instructions on this information sheet.

2.Open the manual gas valve in the heater supply line.

3.Turn on electric power to the heater.

4.Set the thermostat to desired setting (above ambient temperature). The automatic starting sequence begins.

 

TO TURN OFF THE HEATER

 

 

 

 

 

1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner

 

 

 

 

will turn 'OFF' immediately, but fans will continue to cool heat exchanger

 

Fire Hazard

 

until the fan thermostat switches off.

 

 

 

 

 

 

 

 

IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,

Some objects can catch fire or explode when placed

close to heater.

 

 

 

FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER

 

 

 

 

1. Set the thermostat to off or the lowest setting.

 

Keep all flammable objects, liquids and vapors the

 

required clearances to combustibles away from heater.

2. Turn off electric power to the heater.

 

 

 

 

 

 

3. Turn off the manual gas valve in the heater supply line.

Failure to follow these instructions can result in death,

4. Call your installer/contractor qualified in the installation and service

injury or property damage.

 

 

of gas-fired heating equipment.

 

 

 

 

 

 

Installation Clearances

 

Clearances to Combustibles

 

Roof Terminal

 

 

 

 

 

 

 

 

 

 

Top

 

 

Top

 

 

(Optional separated

 

 

 

 

 

 

 

combustion concentric

 

 

 

 

 

 

 

venting shown.)

 

 

 

 

 

 

 

Top*

 

Left

Right

Left

Right

 

 

 

 

 

 

 

Wall

 

10'

 

Bottom

 

 

Bottom

Rear*

(3 m)

 

 

 

 

 

Terminal

 

 

 

 

 

 

 

Max. Mounting Height*

 

Models 30 - 125

 

Models 150 - 400

 

 

 

 

 

 

*Models

30 - 125

150 - 400

Models

 

30 - 125

150 - 400

 

Top

 

1" (2.5 cm)

6" (15 cm)

 

Top

1" (2.5 cm)

6" (15 cm)

 

 

Bottom

 

0" (0 cm)

3" (8 cm)

 

Rear

18" (46 cm)

24" (61 cm)

 

 

Right

 

1" (2.5 cm)

31" (79 cm)*

 

Max Mounting Height1

12' (3.7 m) - 20' (6 m)

20' (6 m) - 30' (9 m)

 

 

Left

 

6" (15 cm)

1Heaters can be mounted higher if destratification fans are installed. See Installation, Operation

 

18" (46 cm)*

Vent

 

2" (5 cm)

2" (5 cm)

and Service Manual for specific mounting height recommendations.

 

* Clearance needed for servicing.

 

 

NOTE: Venting directly from top of heater not applicable on Models 150-400.

 

 

 

 

 

 

Roberts-Gordon, LLC

Telephone: 716.852.4400

 

 

 

 

1250 William Street

 

 

 

 

P.O. Box 44

Fax: 716.852.0854

 

 

 

 

 

Buffalo, NY 14240-0044 USA

Toll Free: 800.828.7450

 

 

 

 

 

Installation Code and Annual Inspections:

All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary, using only replacement parts sold and supplied by Roberts-Gordon.

For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.

Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please contact us for any further information you may require, including the Installation, Operation and Service Manual.

Models 100-400 are not for residential use.

© 2007 Roberts-Gordon, LLC

www.rg-inc.com

Printed in U.S.A.

P/N 91040031 Rev B