Space Requirements for Outdoor Unit
When installing 1 outdoor unit
Figure Description
| Top view |
| Side view | |||
| Air intake | Air outlet |
|
| Air intake | |
|
| |||||
|
|
|
|
| ||
|
|
|
|
|
|
|
| Air outlet |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
, Air ow direction.
(Unit : mm)
When the air outlet is opposite the | When the air outlet is towards the | When 3 sides of the outdoor unit are | |
wall | wall | blocked by the wall |
|
300 or more | 1500 or more | 300 or more |
|
|
| 150 or more | 600 or more |
ENGLISH
The upper part of the outdoor unit and the air outlet is towards the wall
2000 or more | or more |
| 1500 |
The upper part of the outdoor unit and the air outlet is opposite the wall
500 or more | 300 or more |
|
When the walls are blocking front and the rear side of the outdoor unit
1500 or 300 or more more
When installing more than 1 outdoor unit
| (Unit : mm) |
When the air outlet is towards the wall | When 3 sides of the outdoor unit are blocked by the wall |
1500 or more
300 or more
300 or more | 600 or more 600 or more 600 or more |
25