Field Setting Value(FSV) Table

Operating advanced function

FIELD SETTING MODE

Field Setting Value(FSV) Table

Code 10✴✴ : Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)

Code 20✴✴ : Water law design and external room thermostat

Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor & FCU), WL & Thermostat types

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Remote

Water Out Temp for Cooling

Max

✴✴11

25

18

25

1

˚C

Controller

Min

✴✴12

16

5

18

1

˚C

 

Setting Range

 

 

 

 

 

 

 

 

Room Temp for Cooling

Max

✴✴21

30

24

30

1

˚C

 

Code 10✴✴

Min

✴✴22

18

18

22

1

˚C

 

 

Water Out Temp for Heating

Max

✴✴31

55

37

55

1

˚C

 

Min

✴✴32

25

15

37

1

˚C

 

 

 

Room Temp for heating

Max

✴✴41

30

24

30

1

˚C

 

Min

✴✴42

16

16

22

1

˚C

 

 

 

DHW Tank Temp

Max

✴✴51

50

50

70

1

˚C

 

Min

✴✴52

40

30

40

1

˚C

 

 

Water Law

Outdoor Temp for Water Law

Point

✴✴11

-10

-20

5

1

˚C

Code 20✴✴

(Heating)

Point

✴✴12

15

10

20

1

˚C

Water Out Temp for WL1 Heating

Point

✴✴21

40

40

55

1

˚C

 

 

(WL1-Floor)

Point

✴✴22

25

17

37

1

˚C

 

Water Out Temp for WL2 Heating

Point

✴✴31

50

40

55

1

˚C

 

(WL2-Fan Coil Unit)

Point

✴✴32

35

17

37

1

˚C

 

Heating Water Law for Auto Mode

WL Type

✴✴41

1(WL1)

1

2(WL2)

-

-

 

Outdoor Temp for Water Law

Point

✴✴51

30

25

35

1

˚C

 

(Cooling)

Point

✴✴52

40

35

45

1

˚C

 

Water Out Temp for WL1 Cooling

Point

✴✴61

25

18

25

1

˚C

 

(WL1-Floor)

Point

✴✴62

18

5

18

1

˚C

 

Water Out Temp for WL2 Cooling

Point

✴✴71

18

18

25

1

˚C

 

(WL2-Fan Coil Unit)

Point

✴✴72

5

5

18

1

˚C

 

Cooling Water Law for Auto Mode

WL Type

✴✴81

1(WL1)

1

2(WL2)

-

-

 

External Thermostat Application

#1(Floor)

✴✴91

0(No)

0

1(Yes)

-

-

 

#2(FCU)

✴✴92

0(No)

0

1(Yes)

-

-

 

 

30_ Operating advanced function

Page 30
Image 30
Samsung NH200WHXES, NH160PHXEA, NH080PHXEA Field Setting ValueFSV Table, Operating advanced function, Field Setting Mode

FAQ

What is included in the field setting mode?

The field setting mode includes information on upper and lower temperature limits, water law design, and external room thermostat.

How can I adjust the water out temperature for cooling?

You can adjust the water out temperature for cooling by following the instructions in the FSV table under the 'Water Out Temp for Cooling' section.

Where can I find information on the external thermostat application?

Information on the external thermostat application can be found under the 'External Thermostat Application' section.