Operating advanced function

FIELD SETTING MODE

Field Setting Value(FSV) Table

Code 10✴✴ : Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)

Code 20✴✴ : Water law design and external room thermostat

Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor & FCU), WL & Thermostat types

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Remote

Water Out Temp for Cooling

Max

✴✴11

25

18

25

1

˚C

Controller

Min

✴✴12

16

5

18

1

˚C

 

Setting Range

 

 

 

 

 

 

 

 

Room Temp for Cooling

Max

✴✴21

30

24

30

1

˚C

 

Code 10✴✴

Min

✴✴22

18

18

22

1

˚C

 

 

Water Out Temp for Heating

Max

✴✴31

55

37

55

1

˚C

 

Min

✴✴32

25

15

37

1

˚C

 

 

 

Room Temp for heating

Max

✴✴41

30

24

30

1

˚C

 

Min

✴✴42

16

16

22

1

˚C

 

 

 

DHW Tank Temp

Max

✴✴51

50

50

70

1

˚C

 

Min

✴✴52

40

30

40

1

˚C

 

 

Water Law

Outdoor Temp for Water Law

Point

✴✴11

-10

-20

5

1

˚C

Code 20✴✴

(Heating)

Point

✴✴12

15

10

20

1

˚C

Water Out Temp for WL1 Heating

Point

✴✴21

40

40

55

1

˚C

 

 

(WL1-Floor)

Point

✴✴22

25

17

37

1

˚C

 

Water Out Temp for WL2 Heating

Point

✴✴31

50

40

55

1

˚C

 

(WL2-Fan Coil Unit)

Point

✴✴32

35

17

37

1

˚C

 

Heating Water Law for Auto Mode

WL Type

✴✴41

1(WL1)

1

2(WL2)

-

-

 

Outdoor Temp for Water Law

Point

✴✴51

30

25

35

1

˚C

 

(Cooling)

Point

✴✴52

40

35

45

1

˚C

 

Water Out Temp for WL1 Cooling

Point

✴✴61

25

18

25

1

˚C

 

(WL1-Floor)

Point

✴✴62

18

5

18

1

˚C

 

Water Out Temp for WL2 Cooling

Point

✴✴71

18

18

25

1

˚C

 

(WL2-Fan Coil Unit)

Point

✴✴72

5

5

18

1

˚C

 

Cooling Water Law for Auto Mode

WL Type

✴✴81

1(WL1)

1

2(WL2)

-

-

 

External Thermostat Application

#1(Floor)

✴✴91

0(No)

0

1(Yes)

-

-

 

#2(FCU)

✴✴92

0(No)

0

1(Yes)

-

-

 

 

30_ Operating advanced function

Page 30