Operating advanced function
FIELD SETTING MODE
Field Setting Value(FSV) Table
•Code 10✴✴ : Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out, Room), Cooling(Water Out, Room), DHW(Tank)
•Code 20✴✴ : Water law design and external room thermostat
Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor & FCU), WL & Thermostat types
Field Setting Value
Main Menu & | Sub Menu Function | Description | Sub | Default | Min | Max | Step | Unit | |
Code | Code | ||||||||
|
|
|
|
|
|
| |||
Remote | Water Out Temp for Cooling | Max | ✴✴11 | 25 | 18 | 25 | 1 | ˚C | |
Controller | Min | ✴✴12 | 16 | 5 | 18 | 1 | ˚C | ||
| |||||||||
Setting Range |
|
|
|
|
|
|
|
| |
Room Temp for Cooling | Max | ✴✴21 | 30 | 24 | 30 | 1 | ˚C | ||
| |||||||||
Code 10✴✴ | Min | ✴✴22 | 18 | 18 | 22 | 1 | ˚C | ||
| |||||||||
| Water Out Temp for Heating | Max | ✴✴31 | 55 | 37 | 55 | 1 | ˚C | |
| Min | ✴✴32 | 25 | 15 | 37 | 1 | ˚C | ||
|
| ||||||||
| Room Temp for heating | Max | ✴✴41 | 30 | 24 | 30 | 1 | ˚C | |
| Min | ✴✴42 | 16 | 16 | 22 | 1 | ˚C | ||
|
| ||||||||
| DHW Tank Temp | Max | ✴✴51 | 50 | 50 | 70 | 1 | ˚C | |
| Min | ✴✴52 | 40 | 30 | 40 | 1 | ˚C | ||
|
| ||||||||
Water Law | Outdoor Temp for Water Law | Point ➀ | ✴✴11 | 5 | 1 | ˚C | |||
Code 20✴✴ | (Heating) | Point ➁ | ✴✴12 | 15 | 10 | 20 | 1 | ˚C | |
Water Out Temp for WL1 Heating | Point ➀ | ✴✴21 | 40 | 40 | 55 | 1 | ˚C | ||
| |||||||||
| Point ➁ | ✴✴22 | 25 | 17 | 37 | 1 | ˚C | ||
| Water Out Temp for WL2 Heating | Point ➀ | ✴✴31 | 50 | 40 | 55 | 1 | ˚C | |
| Point ➁ | ✴✴32 | 35 | 17 | 37 | 1 | ˚C | ||
| Heating Water Law for Auto Mode | WL Type | ✴✴41 | 1(WL1) | 1 | 2(WL2) | - | - | |
| Outdoor Temp for Water Law | Point ➀ | ✴✴51 | 30 | 25 | 35 | 1 | ˚C | |
| (Cooling) | Point ➁ | ✴✴52 | 40 | 35 | 45 | 1 | ˚C | |
| Water Out Temp for WL1 Cooling | Point ➀ | ✴✴61 | 25 | 18 | 25 | 1 | ˚C | |
| Point ➁ | ✴✴62 | 18 | 5 | 18 | 1 | ˚C | ||
| Water Out Temp for WL2 Cooling | Point ➀ | ✴✴71 | 18 | 18 | 25 | 1 | ˚C | |
| Point ➁ | ✴✴72 | 5 | 5 | 18 | 1 | ˚C | ||
| Cooling Water Law for Auto Mode | WL Type | ✴✴81 | 1(WL1) | 1 | 2(WL2) | - | - | |
| External Thermostat Application | #1(Floor) | ✴✴91 | 0(No) | 0 | 1(Yes) | - | - | |
| #2(FCU) | ✴✴92 | 0(No) | 0 | 1(Yes) | - | - | ||
|
|
30_ Operating advanced function