Remote Controller Setting Range : Code 10✴✴
Field Setting Value
Main Menu & | Sub Menu Function | Description | Sub | Default | Min | Max | Step | Unit | |
Code | Code | ||||||||
|
|
|
|
|
|
| |||
Remote | Water Out Temp for Cooling | Max | ✴✴11 | 25 | 18 | 25 | 1 | ˚C | |
Min | ✴✴12 | 16 | 5 | 18 | 1 | ˚C | |||
Controller | |||||||||
| |||||||||
| Max | ✴✴21 | 30 | 24 | 30 | 1 | ˚C | ||
Setting Range | Room Temp for Cooling | ||||||||
Min | ✴✴22 | 18 | 18 | 22 | 1 | ˚C | |||
|
| ||||||||
Code 10✴✴ | Water Out Temp for Heating | Max | ✴✴31 | 55 | 37 | 55 | 1 | ˚C | |
| Min | ✴✴32 | 25 | 15 | 37 | 1 | ˚C | ||
|
| ||||||||
| Room Temp for heating | Max | ✴✴41 | 30 | 24 | 30 | 1 | ˚C | |
| Min | ✴✴42 | 16 | 16 | 22 | 1 | ˚C | ||
|
| ||||||||
| DHW Tank Temp | Max | ✴✴51 | 50 | 50 | 70 | 1 | ˚C | |
| Min | ✴✴52 | 40 | 30 | 40 | 1 | ˚C | ||
|
|
Space Cooling
•Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC), Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
-With this default FSV settings, user can change the target water outlet temperature within the range of 5 ~ 25ºC for cooling
•Target room temperature : Upper limit(#1021, Default 30ºC, Range : 24 ~ 30ºC),
Lower limit(#1022, Default 18ºC, Range : 18 ~ 22ºC)
-With this default FSV settings, user can change the target room temperature within the range of 18 ~ 30ºC for cooling.
•The #1 DIP switch in the wired remote controller should be set to “OFF”(Default) for cooling operation of heat pump.
•The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the water outlet temperature.
•The #2 DIP switch in the wired remote controller should be set to “ON” to control the room temperature.
•The #3 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the air sensor in remote controller.
•The #3 DIP switch in the wired remote controller should be set to “ON” to control the external air sensor.
Space Heating
•Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC), Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
-With this default FSV settings, user can change the target water outlet temperature within the range of 25 ~ 55ºC for heating.
•Target room temperature : Upper limit(#1041, Default 30ºC, Range : 24 ~ 30ºC),
Lower limit(#1042, Default 16ºC, Range : 16 ~ 22ºC)
-With this default FSV settings, user can change the target room temperature within the range of 16 ~ 30ºC for heating.
•The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the water outlet temperature.
•The #2 DIP switch in the wired remote controller should be set to “ON” to control the room temperature.
DHW Heating
•Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 80ºC), Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
-With this default FSV settings, user can change the target tank temperature within the range of 40 ~ 50ºC for DHW heating.
The FSV #3011 in the wired remote controller should be set to “1(Yes)” to use DHW function.