Operating advanced function
FIELD SETTING MODE
Space Heating : Code 40✴✴
Ts | DHW by Booster Heater Only |
|
|
| |
Tu | #3034 |
|
|
| |
| #4012 | Ta |
Field Setting Value
Main Menu & | Sub Menu Function | Description | Sub | Default | Min | Max | Step | Unit | |
Code | Code | ||||||||
|
|
|
|
|
|
| |||
Heating | Heat Pump | Heating/DHW Priority | ✴✴11 | 0(DHW) | 0 | 1(Heating) | - | - | |
Code 40✴✴ |
| Outdoor Temp for Priority | ✴✴12 | 0 | 20 | 1 | ˚C | ||
| Heating Off | ✴✴13 | 25 | 14 | 35 | 1 | ˚C | ||
|
| ||||||||
|
| Overshoot | ✴✴14 | 2 | 1 | 4 | 1 | ˚C | |
| Backup Heater | Application | ✴✴21 | 1(On) | 0(Off) | 1 | - | - | |
|
| BUH/BSH Priority | ✴✴22 | 0(Both) | 0 | 2(BSH) | 1 | - | |
|
| For | ✴✴23 | 1(On) | 0(Off) | 1 | - | - | |
|
| Threshold Temp | ✴✴24 | 0 | 35 | 1 | ˚C | ||
| Backup Boiler | Application | ✴✴31 | 0(No) | 0 | 1(Yes) | - | - | |
|
| Boiler Priority | ✴✴32 | 0(Off) | 0 | 1(On) | - | - | |
|
| Threshold Temp | ✴✴33 | 5 | 1 | ˚C |
Heat Pump Variables for Space Heating
•FSV #4011 for DHW priority is set to “0(DHW)”(Default) for the first time. In case of “1(Heating)”, the space heating by heat pump has a priority over the DHW heating by heat pump under the low outdoor temperature condition(#4012).
•DHW compensation temperature in case of space heating priority:
At low outdoor temperature, the target temperature of DHW tank will be increased by the temperature difference defined in FSV #3034 to compensate the relatively cold water stored in DHW tank. In this case, the only heat source for DHW tank would be booster heater inside tank, so the lower part of water stored in tank could be cold due to “No operation of heat pump”. The corrected (higher) set point will make sure that the total heat capacity of the water in the tank remains approximately unchanged, by compensating for the colder bottom water layer of the tank (because the heat exchanger coil is not operational) with a warmer top layer.
•Space heating off temperature(FSV #4013, Default “25˚C”, Range 14 ~ 35˚C):
At high outdoor temperature above this value, the space heating will be turned off, to avoid overheating.
•Overshoot temperature(FSV #4014, Default “2˚C”, Range 1 ~ 4˚C): N/A yet
40_ Operating advanced function