Operating advanced function

FIELD SETTING MODE

DHW Heating : Code 30✴✴

TU > THP MAX

 

 

T(C)

 

TU

 

 

#3021

 

 

 

 

 

 

 

 

 

 

THP MAX

 

#3022

 

 

 

 

 

 

THP OFF

 

#3023

 

 

 

 

 

 

 

THP ON

 

 

 

 

 

 

 

 

 

 

 

 

 

TU < THP MAX

T(C)

#3021

 

THP MAX

 

TU=THP OFF

THP ON

Tu : User set temp.

T(C) : Temp. (Celcius)

#3023

1

Heating request 0

1

DHW request 0

DHW(H/P) 1 operation 0

#3024

#3025 #3026

t

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

DHW

Domestic Hot Water

Application

✴✴11

0(No)

0

1(Yes)

-

-

 

Tank

Code 30✴✴

 

 

 

 

 

 

 

Heat Pump

Max Temp

✴✴21

50

45

55

1

˚C

 

 

 

Stop

✴✴22

2

2

10

1

˚C

 

 

Start

✴✴23

5

1

20

1

˚C

 

 

Min Operation

✴✴24

5

0

20

1

min

 

 

Max Operation

✴✴25

30

5

95

5

min

 

 

Interval

✴✴26

3

0

10

0.5

hour

 

Booster Heater

Application

✴✴31

1(On)

0(Off)

1

-

-

 

 

Delay Time

✴✴32

20

20

95

5

min

 

 

Overshoot

✴✴33

0

0

4

1

˚C

 

 

Compensation Temp

✴✴34

10

0

20

1

˚C

 

Disinfection

Application

✴✴41

1(On)

0(Off)

1

-

-

 

 

Interval

✴✴42

Fri

Mon

Sun

1(All)

day

 

 

Start Time

✴✴43

23

0

23

1

o'clock

 

 

Target Temp

✴✴44

70

40

70

5

˚C

 

 

Duration

✴✴45

10

5

60

5

min

 

Power DHW by User

Timer OFF Function

✴✴51

0(Off)

0

1

-

-

 

Input

Timer Duration

✴✴52

60

30

300

10

min

 

Solar Panel

H/P Combination

✴✴61

0(No)

0(No)

1(Yes)

-

-

36_ Operating advanced function