Operating advanced function

FIELD SETTING MODE

Field Setting Value(FSV) Table

Code 40✴✴ : User’s options for heating devices including internal backup heater and external boiler 401: Space/DHW heating priority and control variables

402: Backup/Booster heater priority and control variables

403: Additional backup boiler operating variables

Code 50✴✴ : User’s options for extra functions

501: New target temperatures of each mode by “Outgoing” hot key of remote controller

5021 : Temperature difference between before & after values in “Economic” DHW mode

503: Time-division multi(TDM) variables for combining operation b/w A2A and A2W

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Heating

Heat Pump

Heating/DHW Priority

✴✴11

0(DHW)

0

1(Heating)

-

-

Code 40✴✴

 

Outdoor Temp for Priority

✴✴12

0

-15

20

1

˚C

 

Heating Off

✴✴13

25

14

35

1

˚C

 

 

 

 

Overshoot

✴✴14

2

1

4

1

˚C

 

Backup Heater

Application

✴✴21

1(On)

0(Off)

1

-

-

 

 

BUH/BSH Priority

✴✴22

0(Both)

0

2(BSH)

1

-

 

 

For back-up use only

✴✴23

1(On)

0(Off)

1

-

-

 

 

Threshold Temp

✴✴24

0

-15

35

1

˚C

 

Backup Boiler

Application

✴✴31

0(No)

0

1(Yes)

-

-

 

 

Boiler Priority

✴✴32

0(Off)

0

1(On)

-

-

 

 

Threshold Temp

✴✴33

-15

-20

5

1

˚C

Others

Outing

Water Out Temp for

✴✴11

25

5

25

1

˚C

 

 

Cooling

Code 50✴✴

 

 

 

 

 

 

 

 

Room Temp for Cooling

✴✴12

30

18

30

1

˚C

 

 

 

 

Water Out Temp for

✴✴13

25

15

55

1

˚C

 

 

Heating

 

 

 

 

 

 

 

 

 

 

Room Temp for Heating

✴✴14

16

16

30

1

˚C

 

 

Auto Cooling WL1 Temp

✴✴15

25

5

25

1

˚C

 

 

Auto Cooling WL2 Temp

✴✴16

25

5

25

1

˚C

 

 

Auto Heating WL1 Temp

✴✴17

15

15

55

1

˚C

 

 

Auto Heating WL2 Temp

✴✴18

15

15

55

1

˚C

 

 

Target Tank Temp

✴✴19

30

30

70

1

˚C

 

DHW Saving Mode

Temp Difference

✴✴21

5

0

40

1

˚C

 

TDM Variable

A2A Max Operation Time

✴✴31

30

5

60

5

min

 

 

A2W Min Operation Time

✴✴32

3

0

10

1

min