Samsung NH080PHXEA Operating advanced function, Field Setting Mode, Field Setting ValueFSV Table

Models: NH300WHXES NH200WHXEA NH300WHXEA NH080PHXEA NH160PHXEA NH200WHXES

1 52
Download 52 pages 10.13 Kb
Page 32
Image 32
32_ Operating advanced function

Operating advanced function

FIELD SETTING MODE

Field Setting Value(FSV) Table

Code 40✴✴ : User’s options for heating devices including internal backup heater and external boiler 401: Space/DHW heating priority and control variables

402: Backup/Booster heater priority and control variables

403: Additional backup boiler operating variables

Code 50✴✴ : User’s options for extra functions

501: New target temperatures of each mode by “Outgoing” hot key of remote controller

5021 : Temperature difference between before & after values in “Economic” DHW mode

503: Time-division multi(TDM) variables for combining operation b/w A2A and A2W

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Heating

Heat Pump

Heating/DHW Priority

✴✴11

0(DHW)

0

1(Heating)

-

-

Code 40✴✴

 

Outdoor Temp for Priority

✴✴12

0

-15

20

1

˚C

 

Heating Off

✴✴13

25

14

35

1

˚C

 

 

 

 

Overshoot

✴✴14

2

1

4

1

˚C

 

Backup Heater

Application

✴✴21

1(On)

0(Off)

1

-

-

 

 

BUH/BSH Priority

✴✴22

0(Both)

0

2(BSH)

1

-

 

 

For back-up use only

✴✴23

1(On)

0(Off)

1

-

-

 

 

Threshold Temp

✴✴24

0

-15

35

1

˚C

 

Backup Boiler

Application

✴✴31

0(No)

0

1(Yes)

-

-

 

 

Boiler Priority

✴✴32

0(Off)

0

1(On)

-

-

 

 

Threshold Temp

✴✴33

-15

-20

5

1

˚C

Others

Outing

Water Out Temp for

✴✴11

25

5

25

1

˚C

 

 

Cooling

Code 50✴✴

 

 

 

 

 

 

 

 

Room Temp for Cooling

✴✴12

30

18

30

1

˚C

 

 

 

 

Water Out Temp for

✴✴13

25

15

55

1

˚C

 

 

Heating

 

 

 

 

 

 

 

 

 

 

Room Temp for Heating

✴✴14

16

16

30

1

˚C

 

 

Auto Cooling WL1 Temp

✴✴15

25

5

25

1

˚C

 

 

Auto Cooling WL2 Temp

✴✴16

25

5

25

1

˚C

 

 

Auto Heating WL1 Temp

✴✴17

15

15

55

1

˚C

 

 

Auto Heating WL2 Temp

✴✴18

15

15

55

1

˚C

 

 

Target Tank Temp

✴✴19

30

30

70

1

˚C

 

DHW Saving Mode

Temp Difference

✴✴21

5

0

40

1

˚C

 

TDM Variable

A2A Max Operation Time

✴✴31

30

5

60

5

min

 

 

A2W Min Operation Time

✴✴32

3

0

10

1

min

32_ Operating advanced function

Page 32
Image 32
Samsung NH080PHXEA, NH200WHXES, NH160PHXEA Operating advanced function, Field Setting Mode, Field Setting ValueFSV Table

FAQ

How do I access the field setting mode?

To access the field setting mode, refer to the Main Menu and Sub Menu Function in the official manual.

What are the options for heating devices?

The options for heating devices include internal backup heater and external boiler control variables, as well as space/DHW heating priority settings.

How can I adjust the target temperatures for each mode?

To adjust the target temperatures for each mode, use the Outgoing hot key of the remote controller and refer to code 501 in the official manual.