Booster Heater Variables for Controlling DHW Tank

Booster Heater Variables for Controlling DHW Tank

The FSV #3031 should be set to “1(On)”(Default) to use booster heater as an additional heat source for DHW tank.

Booster heater startup delay timer : In case of DHW request, this timer will delay the operation of booster heater compared to heat pump.

-FSV #3032(Default 20 min., Range 20 ~ 95 min.), In “Power” DHW mode, the delay timer will be neglected, and the booster starts immediately.

-In “Economic” DHW mode, the DHW heating will be conducted only with heat pump.

-#3032 should be smaller than the maximum H/P time(#3025). If the delay time is set too high, it might take very long time for DHW heating.

Temperature difference determining the booster heater OFF temperature(T_BH OFF = Tu + #3033) : FSV #3033, Default 0˚C, Range : 0 ~ 4˚C.

-Temperature difference determining the booster heater ON temperature(T_BH ON = T_BH OFF - 2)

DHW compensation temperature in case of space heating/cooling priority : FSV #3034 will be explained in next page.

The FSV #4022 for booster heater priority should be set to “0(both)”(Default) or “2”(booster) to use booster heater.

If not(backup heater priority), the booster heater can be operated in case of no backup heater demand.

Disinfection Function

The FSV #3041 should be set to “1(On)”(Default) to use disinfection function.

- Scheduling : Day(#3042, Default “Friday”), starting time(#3043, Default “23:00”), target tank temp. (#3044, Default “70˚C”), duration(#3045, Default 10 min.)

Disinfection Function Disinfection function can be performed only with Samsung’s DHW tank installation.

Urgent DHW by User’s Input (Hot Key of Wired Remote Controller)

By default setting(#3061, Default “0(Off)”, Urgent DHW heating will not be turned off automatically before user’s additional key input. If you want to quit urgent DHW function after a certain amount of duration time(#3052, Default “60 min.”, Range 30 ~ 300 min.), change the FSV #3051 to “1(On)”.

Additional Solar Panel Installation for DHW with Heat Pump (Field Option)

By default setting(#3051, Default “1(Yes)”, the DHW heating by solar panel has a priority over the heat pump operation in case of solar panel installation.

ENGLISHOperating advanced function _39

Operating advanced function _39

Page 39
Image 39
Samsung NH300WHXEA Booster Heater Variables for Controlling DHW Tank, Disinfection Function, Operating advanced function

FAQ

What is the default setting for booster heater startup delay timer?

The default setting is 20 minutes, but it can be adjusted within the range of 20 to 95 minutes.

Can the booster heater be operated with no backup heater demand?

Yes, if not set to backup heater priority, the booster heater can be operated in case of no backup heater demand.

Is disinfection function available for all DHW tank installations?

Disinfection function can be performed only with Samsung's DHW tank installation.