Backup Heater Variables for Space Heating

Backup Heater Variables for Space Heating

The FSV #4021 should be set to “1(On)”(Default) to use 2-stage electric backup heater in hydro unit as an additional heat source.

To compensate the lowered heat pump heating performance under very cold weather conditions, the FSV #4023 should be set to “1(On)”(Default).

-The threshold temperature to use backup heater for cold weather compensation: FSV #4024, Default “0˚C”, Range -15 ~ 35˚C

-Above the threshold temperature, the backup heater usage is restricted to save energy consumption.

The FSV #4022 for backup heater priority should be set to “0(both)”(Default) or “1”(backup) to use backup heater. If not(booster heater priority), the backup heater can be operated in case of no booster heater demand.

To use both heaters together at the same time, please check the capacity of the power circuit breaker of your house before.

ENGLISHOperating advanced function _41

External Backup Boiler for Space Heating (Field Option)

The FSV #4031 should be set to “1(Yes)” to use a backup boiler as an additional heat source. By default option(“0(No)), no installation.

Under the installation of backup boiler in your house, you can freely choose the boiler priority(FSV #4032, Default “0(Off)”).

To compensate the lowered heat pump heating performance under very cold weather conditions, the backup boiler will be operating instead of heat pump under the threshold temperature(FSV #4033, Default “-15˚C”, Range -20 ~ 5˚C).

Operating advanced function _41

Page 41
Image 41
Samsung NH300WHXES, NH200WHXES, NH160PHXEA user manual Backup Heater Variables for Space Heating, Operating advanced function

FAQ

How do I set the FSV #4021 for the 2-stage electric backup heater?

You should set the FSV #4021 to 1OnDefault to use the 2-stage electric backup heater in the hydro unit as an additional heat source.

What is the threshold temperature for using the backup heater for cold weather compensation?

The threshold temperature for using the backup heater is controlled by FSV #4024, with a default of 0C and a range of -15 ~ 35C.

How do I use a backup boiler as an additional heat source?

Set the FSV #4031 to 1Yes to use a backup boiler as an additional heat source. By default, the option is set to 0No if there is no installation.